Remote setting function

Pr.59 Remote function selection
Even if the operation panel is located away from the enclosure, you
can use contact signals to perform continuous variable-speed
operation, without using analog signals.
By merely setting this parameter, you can use the acceleration,
deceleration and setting clear functions of the motorized speed
setter (FR-FK).
Pr.59 Setting
RH, RM, RL signal
function
0 (initial value)
Multi-speed setting
1
Remote setting
2
Remote setting
3
Remote setting
*
0Hz
ON
Acceleration
ON
(RH)
Deceleration
ON
(RM)
Clear (RL)
Forward
ON
rotation (STF)
ON
Power supply
*
External running frequency (other than multi-speed) or PU running frequency
Pr.
Pr.
60

Energy saving control selection

V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
Pr.60 Energy saving control selection
Without a fine parameter setting, the inverter automatically
performs energy saving operation.
This inverter is optimum for fan and pump applications
Valid only under V/F control and advanced magnetic flux vector
control.
Pr. 60 Setting
0 (initial value)
Normal operation mode
Energy saving operation mode
In the energy saving operation mode, the inverter
4
automatically controls the output voltage to minimize
the inverter output voltage during a constant
operation.
When setting parameters, refer to the instruction manual (applied) and understand instructions.
Description
Frequency setting
storage function
With
Not used
Not used
(Turning off STF/STR
clears remotely set
frequency used)
When Pr. 59 = 1
When Pr. 59 = 1, 2
When Pr. 59 = 3
When Pr. 59 = 2, 3
Time
ON
ON
ON
ON
ON
ON
Description
Pr.
Pr.
61 to 64, 292, 293

Automatic acceleration/deceleration

Pr.61 Reference current
Pr.63 Reference value at deceleration
Pr.292 Automatic acceleration/deceleration
Pr.293 Acceleration/deceleration individual operation selection
The inverter automatically sets appropriate parameters for
operation.
The inverter operates in the same conditions as when appropriate
values are set in each parameter even if acceleration/deceleration
time and V/F pattern are not set. This operation mode is useful when
you just want to operate, etc. without fine parameter setting.
Even if automatic acceleration/deceleration has been selected,
inputting the jog, RT (second function selection) or X9 (third function
selection) signal during an inverter stop will switch to the normal
operation and give priority to jog operation, second function
selection or third function selection.
After automatic acceleration/deceleration operation has been
started, none of jog signal, RT signal and RT signal are accepted.
Pr.292
Operation
Setting
0
(initial value
normal mode)
1
Without brake
(shortest
resistor and
acceleration/
brake unit
deceleration mode)
11
With brake
(shortest
resistor and
acceleration/
brake unit
deceleration mode)
3
The inverter performs optimum operation fully
(optimum
utilizes its' capability within the continuous
acceleration/
rating range.
deceleration mode)
Stall prevention
5
operation level
(elevator mode 1)
150%
Stall prevention
6
operation level
(elevator mode 2)
180%
With mechanical
7
brake opening
(brake sequence
completion
mode 1)
signal input
Without
8
mechanical
(brake sequence
brake opening
mode 2)
completion
signal input
Use Pr.61 to Pr.63 to change the reference current for the shortest
acceleraiton/deceleration
mode
deceleration mode.
Use Pr.64 to set the starting frequency for the elevator mode.
Calculation
of
acceleration/deceleration
individually.
This function is made valid in the shortest acceleration/deceleraion
mode and optimum acceleration/deceleration mode.
Pr.293 Setting
0 (initial value)
Both acceleraion/deceleration time is calculated.
1
Only acceleration time is calcurated.
2
Only deceleration time is calcurated.
Pr.62 Reference value at acceleration
Pr.64 Starting frequency for elevator mode
Automatic
Setting
Parameter
Set when you want to
accelerate/decelerate the
motor for the shortest time.
Pr.7, Pr.8
(stall prevention operation
level 150%)
Pr.0, Pr.7, Pr.8
Inverter output voltage is
controlled so that enough
Pr.0, Pr.13,
torque can be generated
Pr.19
even under power driving
and regeneration.
Operation mode in which a
machine brake operation
timing signal for vertical lift
applications is output.
and
optimum
acceleraiton/
can
be
performed
Description
50