Func-
Parameter
tion
PID control automatic switchover
127
freqeuncy
128
PID action selection
129
PID proportional band
130
PID integral time
131
PID upper limit
132
PID lower limit
133
PID action set point
134
PID differential time
Commercial power-supply switchover
135
sequence output terminal selection
136
MC switchover interlock time
137
Start waiting time
Commercial power-supply operation
138
switchover selection at an alarm
Automatic switchover frequency
139
between inverter and commercial
power-supply operation
Backlash acceleration stopping
140
frequency
141
Backlash acceleration stopping time
Backlash deceleration stopping
142
frequency
143
Backlash deceleration stopping time
144
Speed setting switchover
145
PU display language selection
148
Stall prevention level at 0V input
149
Stall prevention level at 10V input
150
Output current detection level
Output current detection signal delay
151
time
152
Zero current detection level
153
Zero current detection time
Voltage reduction selection during stall
154
prevention operation
155
RT signal reflection time selection
156
Stall prevention operation selection
157
OL signal output timer
158
AM terminal function selection
Automatic switchover ON range
159
between commercial power-supply and
inverter operation
160
User group read selection
Frequency setting/key lock operation
161
selection
Automatic restart after instantaneous
162
power failure selection
163
First cushion time for restart
164
First cushion voltage for restart
Stall prevention operation level for
165
restart
Output current detection signal
166
retention time
Output current detection operation
167
selection
Name
Setting Range
0 to 400Hz, 9999
10, 11, 20, 21, 50, 51, 60,
61
0.1 to 1000%, 9999
0.1 to 3600s, 9999
0 to 100%, 9999
0 to 100%, 9999
0 to 100%, 9999
0.01 to 10.00s, 9999
0, 1
0 to 100s
0 to 100s
0, 1
0 to 60Hz, 9999
0 to 400Hz
0 to 360s
0 to 400Hz
0 to 360s
0, 2, 4, 6, 8, 10, 102,
104, 106, 108, 110
0 to 7
0 to 220%
0 to 220%
0 to 220%
0 to 10s
0 to 220%
0 to 1s
0, 1
0, 10
0 to 31, 100, 101
0 to 25s, 9999
1 to 3, 5 to 14, 17, 18,
21, 24, 32 to 34, 50,
52, 53
0 to 10Hz, 9999
0, 1, 9999
0, 1, 10, 11
0, 1, 2, 10, 11, 12
0 to 20s
0 to 100%
0 to 220%
0 to 10s, 9999
0, 1
Minimum
Refer
Setting
Initial Value
Increments
Page
0.01Hz
9999
1
10
0.1%
100%
0.1s
1s
0.1%
9999
0.1%
9999
0.01%
9999
0.01s
9999
1
0
0.1s
1s
0.1s
0.5s
1
0
0.01Hz
9999
0.01Hz
1Hz
0.1s
0.5s
0.01Hz
1Hz
0.1s
0.5s
1
4
1
0
0.1%
150%
0.1%
200%
0.1%
150%
0.1s
0s
0.1%
5%
0.01s
0.5s
1
1
1
0
1
0
0.1s
0s
1
1
0.01Hz
9999
1
0
1
0
1
0
0.1s
0s
0.1%
0%
0.1%
150%
0.1s
0.1s
1
0
Customer
to
Setting
58
58
58
58
58
58
58
58
58
58
58
58
58
46
46
46
46
47
58
44
44
58
58
58
58
44
59
44
44
48
58
59
59
49
49
49
49
58
58
32

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents