Ups Specifications; General Specification; Mechanical Specification - Toshiba G8000 SERIES Installation And Operation Manual

480/208 v 100/150 kw
Hide thumbs Also See for G8000 SERIES:
Table of Contents

Advertisement

12

UPS Specifications

12.1

General Specification

Terms
Conforming Standard
Ambient Temperature
relative Humidity
Altitude
Audible noise
Insulation resistance
Insulation breakdown
12.2

Mechanical Specification

nominal Capacity
Cabinet protection
Conformity
exterior paint
panel Thickness
Input/output
Cabling entrance
Ground/Control
wiring entrance
outline Dimension
Unit weight
Shipping weight
Floor loading per
Footprint
Clearance
Heat rejection
*Ip20: Foreign objects that are 12 mm (15/32 in.) or larger are prevented from entering the enclosure of the UpS.
G8000 Series with Isolated output Installation and operation manual
Specification
Ul1778-2001
pF = 1.0: 32 – 86 °F (0 – 30 °C)
pF = 0.8: 32 – 104 °F (0 – 40 °C)
30% – 90%
< 3,280 ft. (< 1,000 m)
68dB (100, 150 kW)
3 MΩ
AC 2 kV – 1 min.
AC 1.5 kV – 1 min.
AC 500 V – 1 min.
Sherwin williams, HHT2-7055, 079 beige Texture
FRONT: 1/16 in. (1.6 mm)
BACK/SIDE/TOP: 3/64 in. (1.2 mm)
boTTom: 1/8 in. (3.2 mm)
FRONT: 43 7/16 in. (1,100 mm)
bACK/SIDe: 0 in. (0 mm)
Top: 15 3/4 in. (400 mm)
non-condensing
Contact Toshiba Technical Support for
installation above 3280 ft. (1000 m)
39 in. (1m) away from front
with 500 V-megger
external Interface
100 kw
IeC298 Ip20*
boTTom
boTTom
W: 36.8 in. (935 mm)
D: 31.8 in. (808 mm)
H: 79.2 in. (2012 mm)
2146 lb. (973 kg))
2236 lb. (1014 kg)
2379 lb./ft.
2
(11,615 kg/m
)
2
34,121 bTU/h
(8598 kcal/h)
remarks
Ul, cUl, IeC
main Circuit
Control Circuit
37

Advertisement

Table of Contents
loading