Ups Connections; Terminal Block - 208/240; Out - Toshiba 1600XPi Series Installation And Operation Manual

Single phase - 3.6/5.2/6/8/10/14/18/22 kva
Hide thumbs Also See for 1600XPi Series:
Table of Contents

Advertisement

7

UPS Connections

7.1
Terminal Block - 208/240 V
The following illustration is a detail view of the terminal block and wiring connections used for 208/240 volt units (see
"Appendix C: 1600XPi Dimensions and Weights" on page C1).
1
2
L1 (L*)
L2 (N*)
208/240 V
in
INPUT
* – If only one input line is hot, connect hot line to terminal 1 (L), and connect the Neutral line to terminal 2 (N).
NOTE 1 – If AC input power is 208 Vac rated, short terminals 11 and 12 with a jumper wire. DO NOT jumper terminal 13 to 12 or 11. Factory Setting is
208 Vac. Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.
NOTE 2 – If AC input power is 240 Vac rated, short terminals 12 and 13 with a jumper wire. DO NOT jumper terminal 11 to 12 or 13. Use the jumper
wire provided by Toshiba. DO NOT add any additional jumpers.
NOTE 3 – EPO and Rmt Contacts function – See Section 8.2
12
, 120/208/240 V
IN
Factory Installed N - G Jumper
3
4
5
6
G
X1
X2
N (0V)
32 V
88 V
120 V
120 V
208 V
240 V
OUTPUT

OUT

1,2
12
7
8
11
X3
G
208
COM 240
208V
240V
Jumper selection
See notes 1&2
1600XPi Series UPS Installation and Operation Manual – 60616-014
13
14
15
16
EPO1
EPO2
REMOTE1
NO
NO
EPO
Rmt Contacts
3
17
REMOTE2
3