Table 2-1 Ups Installation Environment - Toshiba G9400 Series Installation And Operation Manual

Table of Contents

Advertisement

WARNING
The UPS is to be installed in a controlled environment.
Improper storage and installation environment may deteriorate insulation, shorten component life and
cause malfunctions.
Keep the installation environment per standard described as follows:
No
Item
1
Installation location
2
Ambient temperature
3
Relative humidity
4
Altitude
5
Dust
6
Inflammable gas
following
IEC654-4
Part 4
G9400 480V 1200-2000kVA Installation and Operation Manual 203078-001
WARNING 3
4
Table 2–1 UPS Installation Environment
Indoors
Minimum temperature: 32F(0C)
Maximum temperature: 104F(40C)
The relative humidity must be held between 5 and 95%.
There must be no condensation due to temperature changes.
This equipment is designed to operate without derating at 1980m (6500ft) above sea
level.
Dust in the room where the UPS is installed must not exceed normal atmospheric dust
levels. In particular, that dust should not include iron particles, oils or fats, or conductive
materials such as silicone.
There should be no inflammable/explosive gas.
Hydrogen sulfide (H
S)
2
Sulfurous acid gas (SO
2
Chlorine gas (Cl
)
2
Ammonia gas (NH
)
3
Nitrous oxides (NO
)
x
Ozone (O
)
3
Environment standard
No more than 0.003 PPM
)
No more than 0.01 PPM
No more than 0.002 PPM
No more than 1 PPM
No more than 0.05 PPM
No more than 0.002 PPM