4 Individual remote controls
PC-ARH
4.3.4 Checking procedure
1 Switch on the power supply to all indoor units.
2 Models with automatic address function will take three to five minutes to complete the settings.
3 Set the system to "TEST RUN" mode from the outdoor units.
N O T E
•
The PC-ARH does not have Test Run mode. The test run must be carried out from the outdoor unit.
•
It takes 3 to 5 minutes to complete the automatic address setting after the power source is switched on.
•
The total number of units connected is indicated on the liquid crystal display.
•
If the indicated number is incorrect, then there is an abnormal condition such as such as incorrect wiring, electrical noise, etc.
•
Switch off the power source and correct the wiring after checking the following points (wait at least 10 seconds before switching the
power source on/off)
-
The indoor unit power source is not connected or the wiring is incorrect.
-
Incorrect connection of cable between indoor units or incorrect connection of remote control cable.
-
Incorrect setting of rotary switch (setting overlapped) on PCB of the indoor units.
4 Cancelling test run mode
•
Test Run mode will end automatically after 2 hours.
•
Test Run mode can be cancelled from the outdoor unit or by pressing the on/off button on the PC-ARH.
N O T E
The operation mode during the test is stored on the PC-ARH. Once the Test Run is complete, select the operation mode - see "Optional
functions".
165
TCGB0106 rev.0 - 12/2014