Checking Procedure - Hitachi PC-ARF Technical Catalogue

Table of Contents

Advertisement

4 Individual remote controls
PC-ARH

4.3.4 Checking procedure

1 Switch on the power supply to all indoor units.
2 Models with automatic address function will take three to five minutes to complete the settings.
3 Set the system to "TEST RUN" mode from the outdoor units.
N O T E
The PC-ARH does not have Test Run mode. The test run must be carried out from the outdoor unit.
It takes 3 to 5 minutes to complete the automatic address setting after the power source is switched on.
The total number of units connected is indicated on the liquid crystal display.
If the indicated number is incorrect, then there is an abnormal condition such as such as incorrect wiring, electrical noise, etc.
Switch off the power source and correct the wiring after checking the following points (wait at least 10 seconds before switching the
power source on/off)
-
The indoor unit power source is not connected or the wiring is incorrect.
-
Incorrect connection of cable between indoor units or incorrect connection of remote control cable.
-
Incorrect setting of rotary switch (setting overlapped) on PCB of the indoor units.
4 Cancelling test run mode
Test Run mode will end automatically after 2 hours.
Test Run mode can be cancelled from the outdoor unit or by pressing the on/off button on the PC-ARH.
N O T E
The operation mode during the test is stored on the PC-ARH. Once the Test Run is complete, select the operation mode - see "Optional
functions".