4 Individual remote controls
PC-ART

4.2.6.2 Optional functions list

Indi-
Optional Func-
Items
vidual
tion
Setting
Removal of
Heating Tem-
b1
perature Com-
pensation
Circulator
Function at
b2
Heating
Thermo-OFF
3 Minutes OFF
Guard Com-
b3
pressor
Period for
b4
Filter Sign
Fixing of Op-
×
b5
eration Mode
Fixing of Set-
ting Tempera-
×
b6
ture
Fixing Cooling
×
b7
Operation
Automatic
COOL/HEAT
×
b8
Operation
Fixing Fan
×
b9
Speed
Not Prepared
×
bA
Cooling Tem-
perature Com-
bb
pensation
Not Prepared
-
bC
Not Prepared
-
bd
Not Prepared
-
bE
Not Prepared
-
C1
Not Prepared
-
C2
131
TCGB0106 rev.0 - 12/2014
Setting
Condi-
Contents
tion
Standard (Set
00
Temp. +4 ºC)
Removal (Set
01
Temp.)
Set Temp. +2 ºC
02
(*1)
00
Not Available
01
Available
00
Not Available
01
Available
00
Standard
01
100 hours
02
1,200 hours
03
2,500 hours
04
No Indication
00
Not Available
01
Available
00
Not Available
01
Available
00
Not Available
01
Available
00
Not Available
01
Available
00
Not Available
01
Available
"- -"
Not Used
Fixed
Standard (No
00
Compensation)
01
Set Temp. –1 ºC
02
Set Temp. –2 ºC
00
Not Used
(Use as 00 condi-
01
tions)
00
Not Used
(Use as 00 condi-
01
tions)
00
Not Used
(Use as 00 condi-
01
tions)
00
Not Used
(Use as 00 condi-
01
tions)
"- -"
Not Used
Fixed
Indi-
Optional Func-
Items
vidual
tion
Setting
Not Prepared
C3
Drain pump in
C4
heating mode
Static pressure
selection (RPI)
C5
Increased Fan
Speed (RCI,
RCIM, RCD)
Increasing Fan
C6
Speed
Cancelling 3
Minutes Com-
C7
pressor Guard.
Thermistor of
Remote Con-
C8
trol Switch
Not Prepared
-
C9
Not Prepared
-
CA
Selection of
Forced Stop-
×
Cb
page Logic
Not Prepared
×
CC
Not Prepared
Cd
Not Prepared
-
CE
Setting
Condi-
Contents
tion
00
Not Used
(Use as 00 condi-
01
tions)
00
Not available
01
Available
Average static
00
pressure (factory
set)
High static pres-
01
sure
Low static pres-
02
sure
00
Normal
01
Speed increase 1
02
Speed increase 2
00
Not Available
01
Available
00
Available
01
Available
Control by Indoor
00
Suction Thermis-
tor
Control by Ther-
01
mistor of Remote
Control Switch
Control by Aver-
age Value of
Indoor Suction
02
Thermistor and
Thermistor of
Remote Control
Switch
"- -"
Not Used
Fixed
"- -"
Not Used
Fixed
Forced Stoppage
00
Input: A Contact
Forced Stoppage
01
Input: B Contact
00
Not Used
(Use as 00 condi-
01
tions)
00
Not Used
(Use as 00 condi-
01
tions)
00
Not Used
(Use as 00 condi-
01
tions)