M-Net Address Settings - Mitsubishi Electric CMB-WM108V-AA Service Handbook

Hide thumbs Also See for CMB-WM108V-AA:
Table of Contents

Advertisement

[ II Restrictions ]

[4] M-NET Address Settings

Address Settings List
-1- Address Settings List

1. M-NET Address settings

(1) Address settings table
The need for address settings and the range of address setting depend on the configuration of the system.
Unit or controller
CITY MULTI
Main/sub unit
indoor unit
M-NET
adapter
M-NET con-
trol interface
Free Plan
adapter
LOSSNAY
ME remote
Main remote
controller
controller
Sub remote
controller
MA remote controller
CITY MULTI outdoor unit
Auxiliary out-
HBC controller
door unit
(main)
HBC controller
(sub)
*1. If a given address overlaps any of the addresses that are assigned to other units, use a different, unused address within the setting
range.
*2. To set the outdoor unit address or the auxiliary outdoor unit address to "100," set the rotary switches to "50."
*3. To set the ME remote controller address to "200," set the rotary switches to "00."
*4. Some models of indoor units have two or three control boards.
Assign an address to the No.1, No. 2, and No. 3 control boards so that the No. 2 control board address equals the No. 1 control board
address plus 1, and that the No. 3 control board address equals the No. 1 control board address plus 2.
*5. No address settings are required for units in a system with a single outdoor unit (with some exceptions).
Address setting is required if two or more main HBC controllers and a sub HBC controller are connected.
*6. If a given address overlaps any of the addresses that are assigned to other units, use a different, unused address within the setting
range.
HWE1708A
Sym-
Address
bol
setting
range
IC
0, 01 to
Assign the smallest address to the main indoor unit in the
*1 *4 *5 *6
50
group, and assign sequential address numbers to the
rest of the indoor units in the same group.
In a system with two or more HBC controllers, make the
settings for the indoor units in the following order.
(i) Indoor unit to be connected to the main HBC controller 1
(ii) Indoor unit to be connected to sub HBC controller 1
(iii) Indoor unit to be connected to the main HBC controller 2
(iv) Indoor unit to be connected to sub HBC controller 2
Make the settings for the indoor units in the way that the for-
mula "(i) < (ii) < (iii) < (iv)" is true.
LC
0, 01 to
Assign an arbitrary but unique address to each of these units
*1 *4 *5 *6
50
after assigning an address to all indoor units.
RC
101 to 150
Add 100 to the smallest address of all the indoor units in the
same group.
RC
151 to
Add 150 to the smallest address of all the indoor units in the
*3
200
same group.
MA
No address settings required. (The main/sub setting must be made if 2 re-
mote controllers are connected to the system.)
OC
0, 51 to
Assign an address that equals the lowest address of the in-
*1 *2 *5
100
door units in the same refrigerant circuit plus 50.
*6
Assign an address that equals the address of the outdoor
HB1
0, 51 to
*1 *2 *5
HB2
100
unit in the same refrigerant system plus 1.
If a given address overlaps any of the addresses that are
assigned to the outdoor units or to the sub HBC control-
ler, use a different, unused address within the setting
range.
If two or more main HBC controllers are connected, the
automatic address start up function is not available.
Assign an address to both the sub HBC controller that
HS1
51 to 100
*2
HS2
equals the lowest address of the indoor units that are
connected to each of them plus 50.
If a sub HBC controller is connected, the automatic start-
up function is not available.
- 32 -
Setting method
Factory
address
setting
00
00
101
Main
00
00
GB

Advertisement

Table of Contents
loading

Table of Contents