Establishing Connection And Verifying The Ieee C37.118/1344 Communication; Overview; Setting The Pmu Station Communication (Pmu Report); Setting The Pmu Station Communication (Pmu Configuration) - Hitachi Relion RES670 Commissioning Manual

Phasor measurement unit
Hide thumbs Also See for Relion RES670:
Table of Contents

Advertisement

1MRK 511 409-UUS Rev. K
Section 9
9.1

Overview

The IED can support synchrophasor data communication via IEEE C37.118 and/or IEEE1344 with
maximum 8 TCP clients and 6 UDP client groups, simultaneously.
The rear OEM ports are used for IEEE C37.118/1344 communication. The same ports can also be used
for substation bus (IEC 61850-8-1) communication and process bus (IEC/UCA 61850-9-2LE)
communication where applicable.
In order to establish a connection between PMU and a TCP/UDP client (PDC client), an Ethernet
communication link (e.g. optical fiber) shall be available and the required parameters on both PMU and
the TCP/UDP client shall be set. For the purpose of this section, an Open PDC tool (PMU Connection
Tester) installed on a PC is used as the TCP/UDP client.
9.2

Setting the PMU station communication (PMU Report)

1.
Check the settings for the PMU Report parameters by navigating to: Main menu /Configuration /
Communication /Station communication /phasor measurement /PMU Report /PMUREPORT:1
1.1. Make sure that the operation of at least one PMU instance (e.g. PMU1) is Enabled.
1.2. Enable sending the frequency data by setting the parameter SendFreqInfo to Enabled.
2.
Check the operation of the required phasor channels (PHASORREPORT) by navigating to: Main
menu /Configuration /Communication /Station communication /phasor measurement /PMU
Report /PHASORREPORT:x .
9.3
Setting the PMU station communication (PMU
configuration)
To enable IEEE C37.118/1344 communication, the corresponding OEM ports must be activated. The
galvanic Ethernet front port and the rear optical ports can be used for IEEE C37.118/1344
communication.
To enable IEEE C37.118/1344 synchrophasor communication:
1.
Enable communication for by navigating to: Main menu /Configuration /Communication /
Ethernet configuration .
Phasor measurement unit RES670
Commissioning manual
Establishing connection and verifying
the IEEE C37.118/1344 communication
Front port is not available in the IED's with blank front panel. By default, AP1 is available
for engineering.
© 2017 - 2022 Hitachi Energy. All rights reserved

Establishing connection and verifying the IEEE C37.118/1344 communication

Section 9
GUID-EFD77C28-6F7C-4277-8C7E-30E78CC8EFAD v3
GUID-B8DCD7BA-AEBA-4977-89D4-2F18ECE34A2F v1
GUID-B4BA9F74-5E28-42FC-8F33-0BC98D5AE6B0 v3
53

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents