Hitachi Relion RES670 Commissioning Manual page 171

Phasor measurement unit
Hide thumbs Also See for Relion RES670:
Table of Contents

Advertisement

1MRK 511 409-UUS Rev. K
Headline
Invalid value set for PMU Parameters
Invalid phase angle reference
GOOSE is configured on a disabled port
LDCM not running the application image
LDCM rate (2M) is not supported
LDCM version is not accepted
OEM not running the application image
SFP unplugged from the slot
SFP replaced with other type
Non Hitachi Power grids vendor SFP detected
Merging unit has no access point
FPGA version is not accepted
Table continues on next page
Phasor measurement unit RES670
Commissioning manual
© 2017 - 2022 Hitachi Energy. All rights reserved
Explanation
There are two possible error conditions:
Check if the following parameters are set correctly on
PMUREPORT:1 ReportRate or SvcClass or parameter
PRIMVAL:1.FrequencySel is not set as 50Hz / 60Hz.
Check if the following parameters are set correctly on
PMUREPORT:1 ReportRate or SvcClass or RptTimetag or
parameter PRIMVAL:1.FrequencySel is not set as 50Hz /
60Hz.
The selected PhaseAngleRef corresponds to an analog
channel that is not configured. Configure a valid reference
channel.
At least one of the access points configured for GOOSE is
disabled. The port can be disabled either through changing
the access point operation to off or by unchecking the
GOOSE protocol from the access point in the Ethernet
configuration in PCM600 or LHMI.
Enable GOOSE on access points:
<Access Points>, can be any of these: AP_FRONT, AP_1,
AP_2, AP_3, AP_4, AP_5, AP_6,AP_7, AP_8
LDCM in <slot number> is running the factory image
instead of the application image. The factory image is older
than the required FW version and does not contain the
latest updates and fixes.
Reboot the IED. If the problem persists, update the LDCM
firmware or replace the board.
The <firmware version> does not support 2M mode. Set
the LDCM to 64k bit mode.
<device name> firmware version <version string> is not
accepted. The minimum accepted version is <version
string>.
Update the LDCM firmware or replace the board.
OEM in pos <slot number> is running the factory image
instead of the application image. The factory image is older
than the required FW version and does not contain the
latest updates and fixes.
Reboot the IED. If the problem persists, update the OEM
firmware or replace the board.
SFP has been unplugged from the slot.
Check the connection.
Corresponding hardware(s) is set to fail.
Configured and the detected SFP(s) are different.
Corresponding hardware(s) is set to fail.
Restart IED and consider reconfigure of HW modules in
LHMI path: \Main menu\Configuration\Reconfigure HW
modules to get the updated hardware list.
Non Hitachi Power grids vendor SFP detected.
Corresponding hardware(s) is set to fail. Use Hitachi Power
grids approved SFP's.
Merging unit has no access point.
Check AP configuration.
FPGA version is not accepted.
If OEM or NUM FPGA code is of too low version, then
update.
Section 13
Troubleshooting
165