Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
parameters setting can be used. More information regarding TCP communication is available in the
Application manual under section Short guidance for use of TCP.
3.
Set the UDP communication parameters by navigating to: Main menu /Configuration /
Communication /Station communication /phasor measurement /PMU Configuration /
PMUCONF . The first three parameters are related to TCP communication and the rest of
parameters are related to setting of six independent UDP client groups. Each UDP group has eight
parameters. More information regarding UDP communication is available in the Application manual
under section Short guidance for use of UDP. The following steps describes setting parameters for
the first UDP group:
3.1. Enable the first UDP group by setting the parameter SendDataUDP1 to Enabled.
3.2. Set the UDP client IP address by setting the parameter UDPDestAddres1 to 192.168.1.99.
3.3. The default parameter settings can be used for the rest of parameters for the first UDP group.
9.4

Setting the TCP/UDP client communication

As an example of a TCP/UDP client, the openPDC tool (PMU Connection Tester Ver. 4.2.12) from Grid
Protection Alliance is used in this section. Install PMU Connection Tester tool on a PC with Ethernet
network adaptor available. The same PC used for PCM600 can be used to install the PMU Connection
Tester tool.
IEC140000133 V1 EN-US
Figure 9:
The following steps explain how to set the PMU Connection Tester parameters in order to establish an
IEEE C37.118 connection with the PMU:
1.
Set the IP stack on PMU Connection Tester to IPv4. Note that the default IP stack on PMU
Connection Tester tool is IPv6.
64
For the purpose of the communication set-up in this section the LAN IP address of the PC is
used, where the PDC client tool is installed.
PMU Connection Tester tool
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK506371-UUS Rev. M
GUID-6CEE3261-D211-4051-8CA8-5840C27C560E v2
IEC140000133-1-en.vsd
Line distance protection REL670
Commissioning manual