Hitachi Relion 670 Series Commissioning Manual page 216

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
SESRSYN
SESRSYN 3
(Operates on CB3
352)
CB1 52
(SESRSYN 1)
LN1 989
ANSI11000274 V1 EN-US
Figure 53:
11.10.1.5
Completing the test
Continue to test another function or end the test by changing the TESTMODE setting to Disabled.
Restore connections and settings to the original values, if changed for testing purposes.
11.10.2
Autorecloser for 1/2/3-phase operation SMBRREC (79)
Verification of the auto recloser for single-phase, two-phase or three-phase auto reclosing attempts can
be considered to consist of two parts.
One part to verify the internal logic and timing of the auto recloser
One part to verify its interaction with the protection system
210
CBConfig
Section to
setting
be
synchronize
d
breaker-and-
Bus2 –
a-half bus
Line2
alt. CB
Bus2 –
(mirrored)
Line1
Bus2 – Bus1 CB2 252
CB2 252
(SESRSYN 2)
Line 1
Objects used in the voltage selection logic
© 2017 - 2023 Hitachi Energy. All rights reserved
Activated
Activated
B1QCLD
B2QCLD
input on IED
input on IED
from
from
CB2 252
CB1 52
Bus 1
Bus 2
CB3 352
(SESRSYN 3)
LN2 989
Line 2
ANSI11000274.en.v1
1MRK506371-UUS Rev. M
Activated
Activated
Indication
LN1QCLD
LN2QCLD
from
input on IED
input on IED
SESRSYN
from
from
on IED
LN2 989
B2SEL,
LN2SEL
LN1 989
B2SEL,
LN1SEL
B1SEL,
B2SEL
Line distance protection REL670
Commissioning manual
M2377-1042 v5
M12400-2 v12

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rel670

Table of Contents