*1
To use terminals PC and SD for a 24 VDC power supply, check the wiring to avoid short circuit between these terminals.
*2
Terminal input specifications can be changed by analog input specification switchover (Pr.73). This terminal is used for voltage input only.
*3
Terminal input specifications can be changed by analog input specification switchover (Pr.267). To select voltage input (0 to 5 V / 0 to 10
V), set the voltage/current input switch to the "V" position. To select current input (4 to 20 mA), set the voltage/current input switch to the
"I" position (initial setting). To use terminal 4 (current input at initial setting), assign "4" to any parameter from Pr.178 to Pr.184 (Input
terminal function selection) before turning ON the AU signal.
*4
It is recommended to use 2 W 1 kΩ when the frequency setting signal is changed frequently.
*5
Not required when calibrating the scale with the operation panel.
12
PRE-OPERATION INSTRUCTIONS