IEC 61850 has defined data sets and report control blocks to transmit signals for monitoring
purposes. Data sets are also used for GOOSE messages in horizontal communication among IEDs.
The project defines the data objects or single data attributes that should be collected in a data set.
Figure
8
data set.
PCM600 will generate default data sets, based on the current ACT configuration. The default data
sets can be modified or removed in the engineering tools. No RCBs are created automatically by
PCM600. However, the configured IEDs are delivered with RCBs for all default data sets or when
templates are used.
LD0
IEC17000105 V1 EN-US
Figure 8:
General rules for data set configuration:
Switchgear control unit SAM600-IO
Communication protocol manual

Data sets and control blocks

shows a data set where all position information of the apparatuses of a bay are put into one
LLN0
LPHD
CTRL
LLN0
SXCBR1
SCSWI1
SXSW1
SCSWI2
SXSWI2
SCSWI3
SXSWI3
SCSWI4
SXSWI4
SCSWI5
SLGAPC
MON
LLN0
IEC 61850–7–2: Example of a data set for MMS
© 2017 - 2021 Hitachi Power Grids. All rights reserved
CTRL/SXCBR1.Pos FC=ST
CTRL/SXSWI1.Pos FC=ST
CTRL/SXSWI2.Pos FC=ST
CTRL/SXSWI3.Pos FC=ST
Pos
CTRL/SXSWI4.Pos FC=ST
Pos
Pos
Pos
Pos
IEC17000105-1-en.vsd
Data sets and control blocks
SEMOD129786-5 v10
DATA-SET
LD0/LLN0.AppPos
stVal
q
t
Origin