Chapter 6 Specifications; Inverter Rating - Mitsubishi Electric FR-A872-E Instruction Manual

Table of Contents

Advertisement

6
SPECIFICATIONS
This chapter explains the specifications of this product.
Always read the instructions before use.
6.1

Inverter rating

 690 VAC power input
• Inverter
Model FR-A872-[]
Applicable motor capacity
*1
(kW)
Rated capacity
*2
(kVA)
*3
Rated current (A)
Overload current
*4
rating
*5
Rated voltage
Power supply voltage
Control power supply auxiliary input
Permissible control power supply auxiliary
input fluctuation
Protection rating of structure (IEC 60529)
Cooling system
*7
Noise level (dB)
Approx. mass (kg)
*1
Indicates the maximum capacity applicable to voltage of 690 V.
*2
The rated output capacity is the value with respect to 690 V output voltage.
*3
Possible output currents during continuous operation under Real sensorless vector control or Vector control are shown in the table below.
PWM carrier
frequency
2 kHz
4 kHz
The PWM carrier frequency is automatically decreased to 2 kHz for heavy duty applications when operating the motor under Real sensorless
vector control or Vector control with a PWM carrier frequency of more than 6 kHz (Pr.72 ≥ 6). The carrier frequency stays at 4 kHz in fast-response
operation.
*4
The percentage of the overload current rating is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow
time for the inverter and motor to return to or below the temperatures under 100% load.
*5
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range.
However, the maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about
*6
FR-DU08: IP40 (except for the PU connector)
*7
Values measured 1 m in front of the inverter and 1.6 m from the floor.
108
6. SPECIFICATIONS
6.1 Inverter rating
SLD
500
ND (initial setting)
450
SLD
680
ND (initial setting)
612
SLD
569
ND (initial setting)
512
110% 60 s, 120% 3 s (inverse-time characteristics) at surrounding air temperature of
SLD
40°C
150% 60 s, 200% 3 s (inverse-time characteristics) at surrounding air temperature of
ND (initial setting)
40°C
Three-phase 600 to 690 V
849 to 1025 VDC
Single-phase 525 to 690 V, 50/60 Hz
Frequency ±5%, voltage ±10%
*6
Open type (IP00)
Forced air
74
186
05690
SLD
ND
472 A
440 A
284 A
296 A
05690
06470
560
500
773
680
647
569
74
186
06470
SLD
537 A
489 A
323 A
330 A
07150
630
560
855
773
715
647
74
186
07150
ND
SLD
593 A
556 A
357 A
375 A
ND
.