• Use a tinned (plating should not include zinc) crimping terminal to connect the earth (ground) cable. When tightening the
screw, be careful not to damage the threads.
• For use as a product compliant with the Low Voltage Directive, use PVC cable whose size is indicated on
• A large leakage current flows into the protective earth (ground) conductor. The amount of current leakage from the FR-
CC2 and FR-A872 measures 20 mA at maximum (in AC/DC current measuring range specified in IEC 60990). Do not use
earth (ground) wires smaller than those specified in national and local safety regulations regarding leakage currents.
• Use the molded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard.
• DC current may flow from the inverter to a protective earth (ground) conductor. When using a residual current device (RCD)
or residual current monitor (RCM), connect a type B RCD or RCM to the power supply side.
• Use the inverter under the conditions of overvoltage category II (regardless of the earth (ground) condition of the power
supply), or overvoltage category III (inverters must be used with the earth-neutral system power supply) specified in IEC
60664.
To use the inverter under the conditions of pollution degree 2, install it in the enclosure of IP2X or higher.
To use the inverter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher.
• On the input and output of the inverter and the converter unit, use cables of the size and type set forth in EN 60204-1 or
IEC 60364-5-52.
• The operating capacity of the relay outputs (terminal symbols A1, B1, C1, A2, B2, C2) should be 30 VDC, 0.3 A. (Relay
output has basic isolation from the internal circuit of the inverter and the converter unit.)
• Control circuit terminals on
• Environment (For the details, refer to
Surrounding air temperature
Humidity
Maximum altitude
*1
For installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude.
 Branch circuit protection
Provide an appropriate fuse in accordance with the table below.
Converter model
FR-CC2-N450K
FR-CC2-N500K
FR-CC2-N560K
FR-CC2-N630K
*1
"xx" in a model name is "41, 46, 51, or 56".
 Short circuit ratings
Suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes, 690 V maximum.
 Motor overload protection
When using the electronic thermal relay function as motor overload protection, set the rated motor current in Pr.9 Electronic
thermal O/L relay.
118
7. APPENDIX
7.2 Instructions for compliance with the EU Directives
page 30
are safely isolated from the main circuit.
page
24.)
During operation
-10°C to +40°C
95% RH or less
*1
4000 m
*1
Fuse model
Manufacturer
170M6xx5
Bussmann
170M6xx5
Bussmann
170M6xx6
Bussmann
170M6xx7
Bussmann
In storage
-20°C to +65°C
95% RH or less
4000 m
Fuse rating (A)
700 V, 1100 A
700 V, 1100 A
700 V, 1250 A
700 V, 1400 A
page
38.
During transportation
-20°C to +65°C
95% RH or less
10000 m