Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
Directive 2014/30/EU) and concerning electrical equipment for use within specified voltage limits (Low- voltage directive 2014/35/EU). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
1MRS758580 C Introduction Introduction This manual The application manual contains application descriptions sorted per function. The manual can be used to find out when and for what purpose a typical function can be used. Intended audience This manual addresses the protection and control engineer responsible for planning, pre-engineering and engineering.
1MRS758580 C Introduction Contact ABB for information on SMU615 related documentation. Symbols and conventions 1.4.1 Symbols The electrical warning icon indicates the presence of a hazard which could result in electrical shock. The warning icon indicates the presence of a hazard which could result in personal injury.
Introduction 1MRS758580 C 1.4.3 Functions, codes and symbols Table 1: Functions included in the merging unit Function IEC 61850 IEC 60617 IEC-ANSI Measurement Disturbance recorder RDRE1 DR (1) DFR (1) Three-phase current measurement CMMXU1 3I (1) 3I (1) Sequence current measurement CSMSQI1 I1, I2, I0 (1) I1, I2, I0 (1)
Page 13
1MRS758580 C Introduction Function IEC 61850 IEC 60617 IEC-ANSI DCSXSWI2 I <-> O DC (2) I <-> O DC (2) Earthing switch indication ESSXSWI1 I <-> O ES (1) I <-> O ES (1) Other Minimum pulse timer (2 pcs) TPGAPC1 TP (1) TP (1)
SMU615 overview 1MRS758580 C Operation functionality 2.2.1 Optional functions • Arc detection Physical hardware The merging unit consists of two main parts: plug-in unit and case. The content depends on the ordered functionality. Main unit Slot ID Content Module ID Details Plug-in unit X100 Auxiliary power/BO...
1MRS758580 C SMU615 overview Rated values of the current and voltage inputs are basic setting parameters of the merging unit. The binary input thresholds are selectable within the range 16…176 V DC by adjusting the binary input setting parameters. The connection diagrams of different hardware modules are presented in this manual.
SMU615 overview 1MRS758580 C Figure 2: Example of the LHMI 2.4.1 LEDs The LHMI includes a dedicated Ready LED indicator and 11 matrix programmable LEDs on front of the LHMI. The LEDs can be configured with PCM600 and the operation mode can be selected via WHMI or PCM600.
1MRS758580 C SMU615 overview Figure 3: LHMI command push button and RJ-45 communication port Web HMI The WHMI allows secure access to the merging unit via a Web browser. When the Secure Communication parameter in the merging unit is activated, the Web server is forced to take a secured (HTTPS) connection to WHMI using TLS encryption.
SMU615 overview 1MRS758580 C • Locally by connecting the laptop to the merging unit via the front communication port. • Remotely over LAN/WAN. WHMI is enabled by default on the rear port and always enabled (cannot be disabled) on the front port. If the WHMI is accessed locally via the front communication port, the following features are available.
Page 21
1MRS758580 C SMU615 overview events and changes in the merging unit. Both audit trail events and process related events can be examined and analyzed in a consistent method with the help of Event List in WHMI and Event Viewer in PCM600. The merging unit stores 2048 audit trail events to the nonvolatile audit trail.
SMU615 overview 1MRS758580 C PCM600 Event Viewer can be used to view the audit trail events and process related events. Audit trail events are visible through dedicated Security events view. Since only the administrator has the right to read audit trail, authorization must be used in PCM600.
1MRS758580 C SMU615 overview through these protocols. However, some communication functionality, for example, horizontal communication between the merging units, is only enabled by the IEC 61850 communication protocol. The IEC 61850 communication implementation supports all monitoring and control functions. Additionally, parameter settings and disturbance recordings can be accessed using the IEC 61850 protocol.
Page 24
SMU615 overview 1MRS758580 C COM600 SCADA Ethernet switch Ethernet switch IEC 61850 PRP Figure 5: PRP solution In case a laptop or a PC workstation is connected as a non-PRP node to one of the PRP networks, LAN A or LAN B, it is recommended to use a redundancy box device or an Ethernet switch with similar functionality between the PRP network and SAN to remove additional PRP information from the Ethernet frames.
1MRS758580 C SMU615 overview Figure 6: HSR solution 2.7.2 Process bus Process bus IEC 61850-9-2 defines the transmission of Sampled Measured Values within the substation automation system. International Users Group created a guideline IEC 61850-9-2 LE that defines an application profile of IEC 61850-9-2 to facilitate implementation and enable interoperability.
Page 26
SMU615 overview 1MRS758580 C Protection and Substation Control Relay Merging Unit Current Sensors Figure 7: SMU615 sending current measurements as sampled measured values to a protection relay SMU615 Application Manual...
Page 27
1MRS758580 C SMU615 overview Protection and Substation Control Relay Merging Unit Voltage Sensor Current Sensors Figure 8: SMU615 sending voltage measurements as sampled measured values to protection relays SMU615 Application Manual...
Page 28
SMU615 overview 1MRS758580 C Smart Substation Control and Protection Substation Merging Unit with Binary I/0 SMV and GOOSE Current Sensors Figure 9: Smart substation control and protection SSC600 with SMU615 The merging unit supports IEC 61850 process bus with sampled values of analog currents and voltages.
1MRS758580 C SMU615 overview Primary Secondary IEEE 1588 v2 IEEE 1588 v2 master clock master clock (optional) Managed HSR Managed HSR Ethernet Ethernet switch switch IEC 61850 Backup 1588 master clock Figure 10: Example network topology with process bus, redundancy and IEEE 1588 v2 time synchronization The process bus is available for all merging units.
Merging unit variants 1MRS758580 C Merging unit variants Application configurations SMU615 is fully configured to perform its designed primary function in the system as a merging unit and it includes only the relevant functions needed for maximum simplicity. SMU615 is available in two alternative application configurations that can be selected depending on the amount of additional physical interfaces required.
1MRS758580 C Merging unit variants Function IEC 61850 IEC 61850-9-2 LE sampled value sending SMVSENDER Condition monitoring and supervision Circuit-breaker condition monitoring SSCBR Trip circuit supervision TCSSCBR Current circuit supervision CCSPVC Fuse failure supervision SEQSPVC Arc detection ARCDSARC Control Circuit-breaker control CBXCBR Disconnector control DCXSWI...
Merging unit variants 1MRS758580 C 3.1.2 Addition of control functions for primary devices and the use of binary inputs and outputs If extra control functions intended for controllable primary devices are added to the configuration, additional binary inputs and/or outputs are needed to complement the standard configuration.
Page 33
1MRS758580 C Merging unit variants Connection diagrams SMU615 X100 X120 Positive 60 - Current 210V Direction 60 - 210V 60 - 210V 1/5A 1/5A 1/5A 0.2/1A TCS1 TCS2 Light sensor input 1 Light sensor input 2 1) Order selectable -Optional 2) The IED features an automatic short-circuit mechanism in the CT connector when plug-in Light sensor input 3...
Page 34
Merging unit variants 1MRS758580 C SMU615 Positive X130 X100 Current Direction 0.2/1A X131 X132 X133 TCS1 TCS2 Light sensor input 1 Light sensor input 2 1) Order selectable -Optional Light sensor input 3 Figure 12: Connection diagram for application configuration A with SIM0002 module SMU615 Application Manual...
Page 35
1MRS758580 C Merging unit variants SMU615 Positive X130 X100 Current Direction 0.2/1A X131 L1/A X132 L2/B X133 L3/C TCS1 TCS2 Light sensor input 1 Light sensor input 2 1) Order selectable -Optional Light sensor input 3 Figure 13: Connection diagram for application configuration A with SIM0005 module SMU615 Application Manual...
Page 36
Merging unit variants 1MRS758580 C SMU615 X100 X120 Positive 60 - Current 210V Direction 60 - 210V 60 - 210V 1/5A 1/5A 1/5A 0.2/1A TCS1 TCS2 X110 X110 BI 1 HSO1 BI 2 HSO2 BI 3 BI 4 HSO3 BI 5 BI 6 BI 7 BI 8...
Page 37
1MRS758580 C Merging unit variants SMU615 Positive X130 X100 Current Direction 0.2/1A X131 X132 X133 TCS1 TCS2 X110 X110 BI 1 HSO1 BI 2 HSO2 BI 3 BI 4 HSO3 BI 5 BI 6 BI 7 BI 8 Light sensor input 1 Light sensor input 2 1) Order selectable -Optional Light sensor input 3...
Page 38
Merging unit variants 1MRS758580 C SMU615 Positive X130 Current X100 Direction 0.2/1A X131 L1/A X132 L2/B X133 L3/C TCS1 TCS2 X110 X110 BI 1 HSO1 BI 2 HSO2 BI 3 BI 4 HSO3 BI 5 BI 6 BI 7 BI 8 Light sensor input 1 Light sensor input 2 1) Order selectable -Optional...
1MRS758580 C Merging unit variants Application configuration A 3.3.1 Applications The application configuration A is mainly intended for sharing currents and voltages over the process bus in the digital MV switchgear (main or backup). The merging unit with an application configuration is delivered from the factory with default settings and parameters.
Page 40
Merging unit variants 1MRS758580 C Analog input Default usage Connector pins Phase-to-earth voltage UL1 X131:7,8 Phase-to-earth voltage UL2 X132:7,8 Phase-to-earth voltage UL3 X133:7,8 Table 10: Default connections for analog inputs with SIM0005 Analog input Default usage Connector pins Phase A current IL1 X131 L1/A:1,2 Phase B current IL2 X132 L2/B:1,2...
Page 41
1MRS758580 C Merging unit variants Default usage Label description Disturbance recorder triggered Disturb. rec. triggered 3.3.2.2 Default disturbance recorder settings Table 13: Default disturbance recorder analog channels Channel Description Table 14: Default disturbance recorder binary channels Channel ID text Level trigger mode Table continues on the next page SMU615 Application Manual...
Page 42
Merging unit variants 1MRS758580 C Channel ID text Level trigger mode SEQSPVC1_FUSEF_3PH Positive or Rising SEQSPVC1_FUSEF_U Positive or Rising CCSPVC1_FAIL Positive or Rising GNRLLTMS1_ALARM Level trigger off GNRLLTMS1_WARNING Level trigger off SCHLCCH1_CH1LIV Level trigger off SCHLCCH1_LNK1LIV Level trigger off ARCDSARC1_ARC_FLT_DET Positive or Rising ARCDSARC2_ARC_FLT_DET Positive or Rising...
Page 43
1MRS758580 C Merging unit variants Channel ID text Level trigger mode Table continues on the next page SMU615 Application Manual...
Merging unit variants 1MRS758580 C Channel ID text Level trigger mode 3.3.3 Functional diagrams The functional diagrams describe the default input, output, alarm LED and function- to-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements. The analog channels have fixed connections to the different function blocks inside the merging unit’s application configuration.
Page 45
1MRS758580 C Merging unit variants 3.3.3.2 Functional diagrams for disturbance recorder Output signals from the condition monitoring and supervision functions are routed to trigger the disturbance recorder or, alternatively, only to be recorded by the disturbance recorder depending on the parameter settings. Additionally, the selected signals from different functions are also connected to the disturbance recorder.
Page 46
Merging unit variants 1MRS758580 C Current circuit supervision CCSPVC1 BLOCK FAIL CCSPVC1_FAIL ALARM CCSPVC1_ALARM O:15|T:2.5|I:1 Fuse failure supervision SEQSPVC1 BLOCK FUSEF_3PH SEQSPVC1_FUSEF_3PH CB_CLOSED FUSEF_U SEQSPVC1_FUSEF_U DISCON_OPEN MINCB_OPEN O:16|T:2.5|I:1 Supervision alarm SEQSPVC1_FUSEF_3PH SUPERVISION_ALARM SEQSPVC1_FUSEF_U CCSPVC1_ALARM O:17|T:2.5|I:1 Figure 19: Current circuit and Fuse failure supervision functions Three arc detection function stages ARCDSARC1...3 are included as an optional function.
Page 47
1MRS758580 C Merging unit variants The phase voltage inputs to the merging unit are measured by the three-phase voltage measurement function VMMXU1. The sequence voltage measurement VSMSQI1 measures the sequence voltage. The measurements can be seen from the WHMI and they are available under the Measurement menu in the left navigation bar.
1MRS758580 C Merging unit variants 3.3.3.6 Functional diagrams for communication Time synchronization GNRLLTMS1 ALARM GNRLLTMS1_ALARM WARNING GNRLLTMS1_WARNING EXCLKMSTR GNRLLTMS1_EXCLKMSTR Redundant Ethernet channel supervision RCHLCCH1 CHLIV_A RCHLCCH1_CHLIV REDCHLIV_B RCHLCCH1_REDCHLIV LNKLIV_A REDLNKLIV_B IEC61850-9-2 LE sampled values sending SMVSENDER Figure 30: Default communication function connection The IEC 61850-9-2 sampled values sending is enabled by default.
Page 50
Merging unit variants 1MRS758580 C 3.4.2.1 Default I/O connections Connector pins for each input and output are presented in the Merging unit's physical connections section. Table 15: Default connections for analog inputs with AIM0013 Analog input Default usage Connector pins Phase A current IL1 X120:7,8 Phase B current IL2...
Page 51
1MRS758580 C Merging unit variants Table 18: Default connections for binary inputs when the analog input is equipped with AIM0013 Binary input Default usage Connector pins X110-BI1 Circuit breaker closed position indication X110:1,5 X110-BI2 Circuit breaker open position indication X110:2,5 X110-BI3 Circuit breaker truck in (service position) indica- X110:3,5...
Page 53
1MRS758580 C Merging unit variants Channel Description Table 23: Default disturbance recorder binary channels when the analog input is equipped with AIM0013 Channel ID text Level trigger mode CB Closed Level trigger off CB Open Level trigger off DC1 Closed Level trigger off DC1 Open Level trigger off...
Page 54
Merging unit variants 1MRS758580 C Channel ID text Level trigger mode SCHLCCH1_LNK1LIV Level trigger off CBXCBR1_CLOSE_COMMAND Level trigger off CBXCBR1_OPEN_COMMAND Level trigger off ARCDSARC1_ARC_FLT_DET Positive or Rising ARCDSARC2_ARC_FLT_DET Positive or Rising ARCDSARC3_ARC_FLT_DET Positive or Rising GOOSERCV_BIN 0_MASTER_TRIP 1 Level trigger off GOOSERCV_BIN 1_MASTER_TRIP 2 Level trigger off GOOSERCV_BIN 2_MASTER_TRIP 3...
Page 55
1MRS758580 C Merging unit variants Channel ID text Level trigger mode GOOSERCV_BIN 17_AU_CLOSE Level trigger off Table 24: Default disturbance recorder binary channels when the analog input is equipped with SIM0002/SIM0005 Channel ID text Level trigger mode CB Closed Level trigger off CB Open Level trigger off DC1 Closed...
Page 56
Merging unit variants 1MRS758580 C Channel ID text Level trigger mode TRPPTRC1_TRIP Positive or Rising TRPPTRC2_TRIP Positive or Rising TRPPTRC3_TRIP Positive or Rising TRPPTRC4_TRIP Positive or Rising TRPPTRC5_TRIP Positive or Rising CONTROL OFF Level trigger off GNRLLTMS1_ALARM Level trigger off GNRLLTMS1_WARNING Level trigger off SCHLCCH1_CH1LIV...
1MRS758580 C Merging unit variants Channel ID text Level trigger mode GOOSERCV_BIN 5_LOCKOUT_RESET Level trigger off GOOSERCV_BIN 6_AU_OPEN Level trigger off GOOSERCV_BIN 7_AU_CLOSE Level trigger off GOOSERCV_BIN 10_MASTER_TRIP 1 Level trigger off GOOSERCV_BIN 11_MASTER_TRIP 2 Level trigger off GOOSERCV_BIN 12_MASTER_TRIP 3 Level trigger off GOOSERCV_BIN 13_MASTER_TRIP 4 Level trigger off...
Page 58
Merging unit variants 1MRS758580 C 3.4.3 Functional diagrams The functional diagrams describe the default input, output, alarm LED and function- to-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements. The analog channels have fixed connections to the different function blocks inside the merging unit’s application configuration.
Page 60
Merging unit variants 1MRS758580 C Trip circuit supervision function TCSSCBR1 BLOCK ALARM TRPPTRC1_TRIP TCSSCBR1_ALARM TRPPTRC2_TRIP O:56|T:5|I:1 X110_BI2_CB_OPEN TCSSCBR2 O:55|T:2.5|I:2 BLOCK ALARM TCSSCBR2_ALARM O:57|T:5|I:2 Current circuit supervision CCSPVC1 BLOCK FAIL CCSPVC1_FAIL ALARM CCSPVC1_ALARM O:45|T:2.5|I:1 Fuse failure supervision with AIM0013 MODULE option Fuse failure supervision with SIM0002 MODULE option SEQSPVC1 SEQSPVC1...
Page 61
1MRS758580 C Merging unit variants 3.4.3.4 Functional diagrams for control DCSXSWI1 and ESSXSWI1 are of status only type. By default, the status only blocks are connected in the application configuration. The disconnector (CB truck) and line side earthing switch status information is connected to DCSXSWI1 and ESSXSWI1. The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
1MRS758580 C Merging unit's physical connections Merging unit's physical connections Inputs 4.1.1 Energizing inputs 4.1.1.1 Phase currents The merging unit can also be used in single or two-phase applications by leaving one or two energizing inputs unoccupied. However, at least terminals X120:7-8 must be connected.
1MRS758580 C Merging unit's physical connections Table 31: Auxiliary voltage supply Terminal Description X100:1 + Input X100:2 - Input 4.1.3 Binary inputs The binary inputs can be used, for example, to generate a blocking signal, to unlatch output contacts, to trigger the disturbance recorder or for remote control of merging unit's settings.
Merging unit's physical connections 1MRS758580 C The merging unit is provided with connection sockets X13, X14 and X15 only if the optional communication module with light sensor inputs has been installed. If the arc protection option is selected when ordering a merging unit, the light sensor inputs are included in the communication module.
1MRS758580 C Merging unit's physical connections 4.2.2 Outputs for signalling SO output contacts can be used for signalling on start and tripping of the merging unit. On delivery from the factory, the start and alarm signals from all the protection stages are routed to signalling outputs.
Glossary 1MRS758580 C Glossary Analog input Breaker control unit BI/O Binary input/output Binary output Circuit breaker Doubly attached node 1. Direct current 2. Disconnector 3. Double command Double-point control Electromagnetic compatibility Ethernet A standard for connecting a family of frame-based computer networking technologies into a LAN FIFO First in, first out...
Page 75
1MRS758580 C Glossary 1. Manufacturing message specification 2. Metering management system Medium voltage Normally closed Normally open PCM600 Protection and Control IED Manager Power output Parallel redundancy protocol Precision Time Protocol RIO600 Remote I/O unit RJ-45 Galvanic connector type Single attached node SMU615 Substation merging unit Sampled measured values...