7.2 General Specifications
Mains supply (L1, L2, L3):
Supply voltage
Mains voltage low / mains drop-out:
During low mains voltage or a mains drop-out, the drive continues until the intermediate circuit voltage drops below the minimum stop level, which corresponds
typically to 15% below the drive's lowest rated supply voltage. Power-up and full torque cannot be expected at mains voltage lower than 10% below the drive's
lowest rated supply voltage.
Supply frequency
Max. imbalance temporary between mains phases
True Power Factor ()
Displacement Power Factor (cos) near unity
Switching on input supply L1, L2, L3 (power-ups) ≤ unit size 1x
Switching on input supply L1, L2, L3 (power-ups) ≥ unit sizes 2x, 3x
Switching on input supply L1, L2, L3 (power-ups) ≥ unit sizes 4x, 5x, 6x
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 480/600 V maximum.
Motor output (U, V, W):
Output voltage
Output frequency
Switching on output
Accel/Decel Times
*
Dependent on power size.
Torque characteristics:
Starting torque (Constant torque)
Starting torque
Overload torque (Constant torque)
*Percentage relates to the frequency converter's nominal torque.
Cable lengths and cross sections:
Max. motor cable length, screened/armoured
Max. motor cable length, unscreened/unarmoured
Max. cross section to motor, mainsand load sharing*
Maximum cross section to control terminals, rigid wire
Maximum cross section to control terminals, flexible cable
Maximum cross section to control terminals, cable with enclosed core
Minimum cross section to control terminals
* See Mains Supply tables for more information!
Digital inputs:
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Input resistance, R
i
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
200-240 V ±10%, 380-480 V ±10%, , 525-600 V ±10%, 525-690 V ±10%
overvoltage category III / pollution degree 2
AF-600 FP Design Guide
50/60 Hz ±5%
3.0 % of rated supply voltage
≥ 0.9 nominal at rated load
(> 0.98)
maximum twice/min.
maximum once/min.
maximum once/2 min.
7
0 - 100% of supply voltage
0 - 1000 Hz
*
Unlimited
1 - 3600 sec.
*
maximum 110% for 1 min.
maximum 135% up to 0.5 sec.
*
*
maximum 110% for 1 min.
150 m
300 m
2
2
1.5 mm
/16 AWG (2 x 0.75 mm
)
1 mm
2
/18 AWG
0.5 mm
2
/20 AWG
2
0.25 mm
4 (6)
18, 19, 27
1)
, 29, 32, 33,
PNP or NPN
0 - 24 V DC
< 5 V DC
> 10 V DC
> 19 V DC
< 14 V DC
28 V DC
approx. 4 kΩ
145