5.1.12 Lead Pump Alternation Wiring Diagram
5
Every pump must be connected to two contactors (K1/K2 and K3/K4) with a mechanical interlock. Thermal relays or other motor protection devices must be
applied according to local regulation and/or individual demands.
RELAY 1 (R1) and RELAY 2 (R2) are the built-in relays in the frequency converter.
When all relays are de-energized, the first built in relay to be energized will cut in the contactor corresponding to the pump controlled by the relay. E.g.
RELAY 1 cuts in contactor K1, which becomes the lead pump.
K1 blocks for K2 via the mechanical interlock preventing mains to be connected to the output of the frequency converter (via K1).
Auxiliary break contact on K1 prevents K3 to cut in.
RELAY 2 controls contactor K4 for on/off control of the fixed speed pump.
At alternation both relays de-energizes and now RELAY 2 will be energized as the first relay.