GE AF-600 FP Design Manual page 132

Fan and pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

Bit 04, No error/error (no trip):
Bit 04 = '0': The frequency converter is not in fault mode. Bit 04 = "1": The frequency converter shows an error but does not trip.
Bit 05, Not used:
Bit 05 is not used in the status word.
Bit 06, No error / triplock:
Bit 06 = '0': The frequency converter is not in fault mode. Bit 06 = "1": The frequency converter is tripped and locked.
Bit 07, No warning/warning:
Bit 07 = '0': There are no warnings. Bit 07 = '1': A warning has occurred.
Bit 08, Speed≠ reference/speed = reference:
Bit 08 = '0': The motor is running but the present speed is different from the preset speed reference. It might e.g. be the case when the speed accels/decels during
start/stop. Bit 08 = '1': The motor speed matches the preset speed reference.
Bit 09, Local operation/bus control:
Bit 09 = '0': [STOP/RESET] is activate on the control unit or Local control in par. F-02 Operation Method is selected. You cannot control the frequency converter via
serial communication. Bit 09 = '1' It is possible to control the frequency converter via the network / serial communication.
Bit 10, Out of frequency limit:
Bit 10 = '0': The output frequency has reached the value in par. F-18 Motor Speed Low Limit [RPM] or par. F-17 Motor Speed High Limit [RPM]. Bit 10 = "1": The output
frequency is within the defined limits.
Bit 11, No operation/in operation:
Bit 11 = '0': The motor is not running. Bit 11 = '1': The frequency converter has a start signal or the output frequency is greater than 0 Hz.
Bit 12, Drive OK/stopped, autostart:
Bit 12 = '0': There is no temporary over temperature on the inverter. Bit 12 = '1': The inverter stops because of over temperature but the unit does not trip and will
resume operation once the over temperature stops.
Bit 13, Voltage OK/limit exceeded:
Bit 13 = '0': There are no voltage warnings. Bit 13 = '1': The DC voltage in the frequency converter's intermediate circuit is too low or too high.
Bit 14, Torque OK/limit exceeded:
Bit 14 = '0': The motor current is lower than the torque limit selected in par. F-43 Current Limit. Bit 14 = '1': The torque limit in par. F-43 Current Limit is exceeded.
Bit 15, Timer OK/limit exceeded:
Bit 15 = '0': The timers for motor thermal protection and thermal protection are not exceeded 100%. Bit 15 = '1': One of the timers exceeds 100%.
NB!
All bits in the STW are set to '0' if the connection between the Interbus option and the frequency converter is lost, or an internal communication problem has
occurred.
AF-600 FP Design Guide
6
131