6.1.3 Frequency Converter Hardware Setup
Use the terminator dip switch on the main control board of the frequency
converter to terminate the RS-485 bus.
NB!
The factory setting for the dip switch is OFF.
6
6.1.4 Frequency Converter Parameter Settings for Modbus Communication
The following parameters apply to the RS-485 interface (drive-port):
Parameter
Number
O-30
O-31
O-32
O-33
O-35
O-36
O-37
106
Parameter name
Function
Protocol
Select the application protocol to run on the RS-485 interface
Address
Set the node address. Note: The address range depends on the protocol selected
in par. O-30 Protocol
Baud Rate
Set the baud rate. Note: The default baud rate depends on the protocol selected
in par. O-30 Protocol
PC port parity/Stop bits
Set the parity and number of stop bits. Note: The default selection depends on the
protocol selected in par. O-30 Protocol
Min. response delay
Specify a minimum delay time between receiving a request and transmitting a
response. This can be used for overcoming modem turnaround delays.
Max. response delay
Specify a maximum delay time between transmitting a request and receiving a
response.
Max. inter-char delay
Specify a maximum delay time between two received bytes to ensure time-out if
transmission is interrupted.
Terminator Switch Factory Setting
AF-600 FP Design Guide