GE AF-600 FP Design Manual page 116

Fan and pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

6.5.1 Writing a Parameter Value
Change par. F-15 Motor Speed High Limit [Hz] to 100 Hz.
Write the data in EEPROM.
PKE = E00F Hex - Write single word in par. F-15 Motor Speed High Limit [Hz]
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 03E8 Hex - Data value 1000, corresponding to 100 Hz, see Con-
version.
The telegram will look like this:
Note: Par. F-15 Motor Speed High Limit [Hz] is a single word, and the parameter
command for write in EEPROM is "E". Parameter number F-15 is 00F in hex-
adecimal.
The response from the slave to the master will be:
6.5.2 Reading a Parameter Value
Read the value in par. F-07 Accel Time 1
PKE = 1007 Hex - Read parameter value in par. F-07 Accel Time 1
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 0000 Hex
If the value in par. F-07 Accel Time 1 is 10 s, the response from the slave to
the master will be:
NB!
3E8 Hex corresponds to 1000 decimal. The conversion index for par. F-07 Accel Time 1 is -2, i.e. 0.01.
par. F-07 Accel Time 1 is of the type Unsigned 32.
AF-600 FP Design Guide
6
115