Product overview

2.2 Functions

Maximum configuration
● 512 bytes I/O data per station
● The integrated power supply of the interface module feeds 14 W into the backplane bus.
Up to 12 I/O modules can be supplied this way. The exact number of operable modules is
determined by the power budget (see relevant section in the ET 200MP distributed I/O
system (http://support.automation.siemens.com/WW/view/en/59193214) system manual).
● A maximum of one power supply module (PS) upstream from the interface module and
two downstream from the interface module is possible.
● If you use a power supply module (PS) upstream from the interface module, the
maximum possible configuration is a total of 32 modules (up to 30 modules downstream
from the interface module).
2.2
Functions
2.2.1

PROFINET IO

Introduction
The interface module supports the following PROFINET IO functions:
● Integrated switch with 2 ports
● Supported Ethernet services: ping, arp, network diagnostics (SNMP)/MIB-2, LLDP
● Port diagnostics
● Disabling ports
● Isochronous real-time communication
● Minimum update time 250 μs
● Prioritized startup
● Device replacement without PG
● Media redundancy (MRP)
● Shared device with up to two IO controllers (when using GSD file for configuration)
● Isochronous mode of process data
● Identification data I&M 0 to 3
● Firmware update via PROFINET IO
● Reset to factory settings via PROFINET IO
● Configuration control (option handling)
10
IM 155-5 PN ST interface module (6ES7155-5AA00-0AB0)
Manual, 08/2013, A5E03612323-02