Maximum number for recording disturbance phenomena
8.3.3
Note that the maximum number for recording the disturbance phenomena depends on the
recording time and the sampling rate. Table 8.3-1 illustrates the maximum number. For
example, 128 phenomena can be memorized in the disturbance recorder, if the function
operates in 50Hz system. The user can also check the maximum number on the IED screen
(See Figure 8.3-2).
Table 8.3-1 Max number depending on time settings
Recording
period set with
[Record Time]
1 sec
3 sec
5 sec
Note: The maximum number is dependent on the VCT type and the software model
selected in the 'Software selection'.
Number of analog quantities and logical signals for disturbance recorder
8.3.4
Ten analog quantities and 256 logical signals are record for one disturbance phenomenon.
Recording items about analog quantities
(i)
The disturbance recorder can record currents and voltages quantities:
Voltage for autoreclosing checking
Recording items
(ii)
During the disturbance recorder running, it can hold the traces of logic signals. The user can
select 256 logic signal randomly with settings [Binary Signal*]. The selected logic signals can
be identified with preferred names, which the user can set with settings [Binary Sig.Name*].
Table 8.3-3 etc. tabulate all settings. For example, 'CB_CLOSE' signal of the PROT_COMM
function may be selected to record with setting [Binary Signal4]; then, the user can name it
'CB_CLOSE' with setting [Binary Sig.Name4].
Max. recording number for Disturbance phenomena
50Hz sys.
255
128
85
Table 8.3-2 Analog recording items
Recording items
Phase currents
Zero-sequence phase current
Phase to phase voltages
Phase voltages
Zero-sequence phase voltage
- 633 -
60Hz sys.
Model GRE200-
1
2
Ia
Ib
Ic
Ie
NA
Ise
NA
Vab
Vbc
Vca
Va
Vb
Vc
Ve
Vs
6F2T0200 (0.15)
255
113
68
GRE200 (1,2)