Mitsubishi Electric MELSEC iQ-R Series Manual page 29

Intelligent function module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

CITL_EntryTimerEvent
This function registers a timer event.
■ Format
short CITL_EntryTimerEvent (long* plEvent)
■ Argument
Argument
Name
plEvent
Registered event
The specification method of the registered event (plEvent) is as follows:
Specification
Description
position
plEvent[0]
Number of timer event settings (1 to 16)
plEvent[1]
First timer event number (1 to 16)
plEvent[2]
Cycle of the first timer event (Clear: 0, Cycle: 1 to 60,000 [ms])
plEvent[3]
Synchronization type of the first timer event (Batch synchronization: 0, Individual
synchronization: 1)
plEvent[4]
Second timer event number (1 to 16)
plEvent[5]
Cycle of the second timer event (Clear: 0, Cycle: 1 to 60,000 [ms])
plEvent[6]
Synchronization type of the second timer event (Batch synchronization: 0, Individual
synchronization: 1)
plEvent[7]
Third timer event number (1 to 16)
plEvent[8]
Cycle of the third timer event (Clear: 0, Cycle: 1 to 60,000 [ms])
plEvent[9]
Synchronization type of the third timer event (Batch synchronization: 0, Individual
synchronization: 1)
plEvent[46]
16th timer event number (1 to 16)
plEvent[47]
Cycle of the 16th timer event (Clear: 0, Cycle: 1 to 60,000 [ms])
plEvent[48]
Synchronization type of the 16th timer event (Batch synchronization: 0, Individual
synchronization: 1)
When setting the timer event cycle, only the following specification method is applicable.
• For 1 to 1000: Specify multiples of 5 (5 ms units)
• For 1000 to 60,000: Specify multiples of 1000 (1 s units)
Description
Specify a timer event to be registered.
3.1 C Intelligent Function Module Dedicated Functions
IN/OUT
IN
First timer event setting
Second timer event setting
Third timer event setting
16th timer event setting
3 DETAILS OF FUNCTION
3
27

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r c