■ Description
• This function writes data to a device, which is specified to the randomly selected device (plDev), of a module specified to
the network number (lNetNo), the start I/O number (lIoNo), the station number (lStNo), and the CPU number (sCPU).
• The data to be written is stored to the write data storage destination (psBuf) in word units. A bit device and a word device
are stored per 1 point, and a double-word device is stored in word units.
• Specify so that the total number of write points specified for each block is 10240 points or less. Otherwise, a size error (-5)
will occur.
• Note that the extension comment information will be deleted when the data is written to the block to which an extension
comment is assigned (extension file register).
• Also, note that sub 2 or sub 3 program will be deleted when data is written to a block (extension file register) overlapping
with the program setting area for sub 2 or sub 3.
• When '0' is specified to the label code (ullLbCode), the device is written without checking the label code.
■ Example
The following tables show the examples of values specified to the randomly selected device (plDev) and the write data
storage destination (psBuf), and the number of bytes of write data.
Device to be written randomly
M100
D10 to D13
LCN100 to LCN101
Values specified to the randomly selected device (plDev)
Setting target
Specified value
plDev[0]
3
plDev[1]
DevM
plDev[2]
100
plDev[3]
1
plDev[4]
DevD
plDev[5]
10
plDev[6]
4
plDev[7]
DevLCN
plDev[8]
100
plDev[9]
2
Data specified for the write data storage destination (psBuf)
Write position
Specified value
psBuf[0]
0
psBuf[1]
10
psBuf[2]
200
psBuf[3]
300
psBuf[4]
400
psBuf[5]
0x0001
psBuf[6]
0x0000
psBuf[7]
0x0000
psBuf[8]
0x0001
Number of bytes of write data
(psBuf[0] to psBuf[8] = 9)  2 = 18
Current value
Turns the bit OFF.
Stores 10 in D10, 200 in D11, 300 in D12, and 400 in D13.
Stores 0x1 in LCN100, and 0x10000 in LCN101.
Description
Number of blocks = 3
Device type = M
Start device number = 100
Number of write points = 1
Device type = D
Start device number = 10
Number of write points = 4
Device type = LCN
Start device number = 100
Number of write points = 2
Description
Turns the bit device for M100 OFF.
D10=10
D11=200
D12=300
D13=400
Lower bit of LCN100 = 0x0001
Upper bit of LCN100 = 0x0000
Lower bit of LCN101 = 0x0000
Upper bit of LCN101 = 0x0001
Block
Block 1: M100
Block 2: D10 to D13
Block 5: LCN100 to LCN101
3 DETAILS OF FUNCTION
3.2 MELSEC iQ-R Series Data Link Functions
3