10. Installation

Electrical wiring work

• When installing outdoor units in module, select the power supply cable according to the sum of outdoor unit
capacity. (Refer to the table for each model)
• Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 66 / CENELEC: H07RN-F)
Ex.) AM500✴XVA✴✴
AM220✴XVA✴✴ AM160✴XVA✴✴ AM120✴XVA✴✴
ELCB
or
MCCB+
ELB
• This device is intended for the connection to a power supply system with a maximum permissible
system impedance shown in the table (on the left page) at the interface point (power service box) of
NOTE
the user's supply.
• The user must ensure that this device is connected only to a power supply system which fulfills the
requirement above. If necessary, the user can ask the public power supply company for the system
impedance at the interface point.
• This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater
than or equal to Ssc(*2) at the interface point between the user's supply and the public system. It is
the responsibility of the installer or user of the equipment to ensure, by consultation with the distri-
bution network operator if necessary, that the equipment is connected only to a supply with a short-
circuit power Ssc greater than or equal to Ssc(*2).
[Ssc (*2)]
Model
AM140KXVAG✴
AM160KXVAG✴
AM180KXVAG✴
AM200KXVAG✴
AM220KXVAG✴
Model
AM140KXVGG✴
AM160KXVGG✴
AM180KXVGG✴
AM200KXVGG✴
AM220KXVGG✴
Ssc [MVA]
5.3
7.6
9.3
8.1
8.6
Ssc [MVA]
5.3
7.6
9.3
8.1
8.6
AM500✴XVA✴✴ : 35 mm
AM280✴XVA✴✴ : 16 mm
AM120✴XVA✴✴ : 4 mm
Model
AM240KXVAG✴
AM260KXVAG✴
AM280KXVAG✴
AM300KXVAG✴
Model
AM240KXVGG✴
AM260KXVGG✴
AM280KXVGG✴
AM080KXVSG✴
2
2
2
Ssc [MVA]
13
13.8
16.2
17.7
Ssc [MVA]
13
13.8
16.2
17.7
129