Free space requirements

The flange-mounted drives can be installed side by side. The free space
requirements above and below the drives are shown below. For additional
requirements, refer to sections
Additional requirements for cabinet installations (page
Note: The free space requirements below are for the heat sink side of the mounting
plate. There is no free space requirement for the front side of the mounting plate.
That area can be occupied by other equipment (e.g., contactors, relays, wires,
ducts, etc.).
Frame
R1 ... R2
R3 ... R5
R6 ... R9
Examining the installation site (page 13)
A
mm
in
100
3.94
115
4.53
200
7.87
Mechanical installation – General 15
16).
mm
200
200
300
and
B
in
7.87
7.87
11.81