Fixed Output Current By Digital Lcd Integral Display; Fixed Output Current By Cometer; Fixed Output Current By Hht; Fixed Output Current By Pc - ABB 2600T Pressure Transmitter Series User Manual

Table of Contents

Advertisement

364xS User's Manual

Fixed output current by Digital LCD Integral Display

To set 4 mA fixed output current
Navigate the Digital LCD Integral Display menu, select
Digital LCD Integral Display Keys sequence to set 4 mA fixed output current: 7 – 2 – 1
To set 20 mA fixed output current
Navigate the Digital LCD Integral Display menu, select
fixed output current. Confirm.
Digital LCD Integral Display Keys sequence to set 20 mA fixed output current: 7 – 2 – 2
To set any fixed output current
Navigate the Digital LCD Integral Display menu, select
the fixed output current values will be available. Select the desired value and confirm.
Digital LCD Integral Display Keys sequence to set any fixed output current: 7 – 2 – 3

Fixed output current by CoMeter

Set of the Fixed output current by CoMeter is available with the 695 Field Indicator. Please refer to the
device manual for the appropriate operations.

Fixed output current by HHT

Set of the Fixed output current by Hand Held Terminal is available. Please refer to the device manual for the
appropriate operations.

Fixed output current by PC

Set of the Fixed output current by PC is available using dedicated Software. ABB can provide the references
and the Software. Please refer to the Software instructions for the appropriate operations.

Hardware settings

Write protect mode

Changes can be prevented to the transmitter configuration data with the write protection electronics dip
switch 2. If the transmitter write protection is activated the transmitter will not accept any writes to its
memory. Configuration changes, such as trim and reranging cannot take place. In case the Digital LCD
Integral Display is installed (no access to switch), the Write protect mode can also be set by HART command
using the HHT and the PC. Please refer to the device manual and Software instruction for the right
operation.
Position the right dip switch in ON to prevent accidental or deliberate
change of configuration data.
Position the right dip switch in OFF to change the configuration data. If
data configuration is not allowed check the Software Write lock using
the HHT or PC.

Change the failsafe direction

The transmitter alarm direction is set by repositioning the electronics dip switch 1. The output value is in
accordance with NE43 NAMUR recommendations.
Diagnostics
>
Loop Test
Diagnostics
>
Loop Test
Diagnostics
>
Loop Test
37
>
Set 4 mA.
Confirm.
>
Set 20 mA
for 20 mA
>
Set Custom Value
and
ON
OFF
ON
OFF
Configuration

Hide quick links:

Advertisement

Table of Contents