Section 4: Electrical Installation
Controller Description
Controller Specification
Ambient temperature
Max. relative humidity
Input voltage range
Protection class
Transient over voltage
Pollution degree
For energy and alarm installation management please see
section 8
A circuit breaker or switch must be installed near the
dryer. This should be easy to reach and shall be certified
according to EN60947-1 and EN60947-3. The switch
or circuit breaker shall be marked as the disconnecting
device for the dryer and needs to be marked with on and
off positions.
Output connections do not provide isolation from the
mains connectors and interconnecting wiring must meet
EN61010-1:2001 requirements for reinforced insulation.
Heatless Desiccant Dryers |
Instruction Manual
35°F to 122°F (1.5°C to 50°C)
80% up to 87.8°F, decreasing linearly to 50% RH at 122°F
100–240VAC, 50–60Hz, 12–24VDC
Mains supply voltage not to exceed ±10% of nominal
IP65
IEC 60664 Class II
2, IEC 60664