NO.F002 Fire Extinguishing System Conceptual Diagram (CE) - 2
-
+
+
E
ROV
SIL
AL
AUX
REMOTE
24V
CONTROL
Technical requirements:
1.
All fire extinguishing signal cables are red (BOM number: 25030029) and black (BOM number: 25030073) cables with naked crimping single-wire cord end terminals (BOM number: 14170214). The red cable is positive and the black cable is
negative. The pneumatic switch, Warning signs, and fire alarm bell each has two wiring terminals that connect to two wires. The fire alarm bell is polarity insensitive. For details, see the diagram.
2.
Connect a 10K terminal resistor to each of the last the fire alarm sounder and fire alarm horn/strobe in parallel.
3.
Connect cables to the smoke detector and heat detector by referring to the diagram. Connect a 6.8 K terminal resistor to the last smoke and heat detectors in parallel.
4.
Connect the emergency abort button and pneumatic switch to a 6.8 K terminal resistor in parallel, and to a 470 ohm resistor in serial. Connect an electrical actuator to a 1N4004 diode in parallel.
5.
Alarm signals are reported to the monitoring system over shielded straight-through network cables. The connection definitions are as follows: LOCAL FIRE, FIRE RELAY, and FAULT RELAY. The signal cables connect to the
ECC over dry contacts.
6.
Attach cable labels to all cables connected to the extinguishant control panel and wiring terminals on electrical actuators and pneumatic switches. See the label table for the label content. Cable direction labels must be
arranged neatly in the same direction. Cables must be bound neatly, with cable ties in the same direction. (Labels are printed on label paper with the BOM number 29041061, attached on cable ties with the BOM number
21200708, and bound to corresponding cables.)
red
L1 IN
L1 IN
-R
red
L1 OUT
L1 OUT
L2
black
black
red
L1 IN
-R
red
L1 OUT
L2
black
black
red
black
red
black
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
FLT
RST
DATA
POWER
S1
S2
ZONE 1
ZONE 2
ZONE 3
2ND
SOUNDER
STATUS UNITS
Connect the first
Data cable
Connect smoke
Connect heat
Power cable
stage alarm to the
detector in
detector in
Connect the second stage alarm to
fire alarm bell.
detection zone 1
detection zone 2
the horn strobes and warning signs .
L1 IN
L1 IN
L1 IN
-R
-R
-R
-R
L1 OUT
L1 OUT
L1 OUT
L1 OUT
L2
L2
L2
L2
L1 IN
L1 IN
L1 IN
L1 IN
-R
-R
-R
-R
L1 OUT
L1 OUT
L1 OUT
L1 OUT
L1 OUT
L2
L2
L2
L2
-
+
-
+
-
+
-
+
-
+
-
NC
C
NO
NC
C
NO
1ST
2ND
MODE
MAN
HOLD
REL
EXTING
STAGE
STAGE
SELECT
RELEASE
PRESS
SWITCH
Connect the
Connect the pressure
Connect the electrical
emergency
signal to the pneumatic
actuator drive signal to the
abort port to
electrical actuator.
switch.
the Extinguishant
abort button .
brown & white
green
brown & white
brown & white
green
green
+
-
NO
C
NC
C
NO
NC
C
NO
NC
C
NO
LOW
EXTRACT
FAULT
LOCAL
FIRE
PRESS
RELAY
FIRE
RELAY
SWITCH
Connect the fault signal
Connect the gas release
Connect the fire alarm
signal output (NO) to the
output (NO) to the
signal output (NO) to the
collector of the monitoring
collector of the monitoring
collector of the monitoring
system.
system.
system.