Extinguishant Control Panel electric heater DLXELL XR02CX thermostat initial configuration parameters
Set Category
SET
Set Point
Hy
Differential
AC
Anti-short cycle delay
Adjusting Parameters
Cy
Compressor ON time faulty probe
Cn
Compressor OFF time faulty probe
CH
Kind of action (Cooling cL, Heating Ht)
id
Interval between defrost cycles
Md
Maximum length for defrost
defrost parameter
Display during defrost ( rt= Actual storage temperature; it= Store temperature
dF
before frost start; St=Set Point; dF="dF", thawing character)
Setting Item
Default value
Setting the threshold
/
-55 - 99 ℃
2.0°C
0.1 - 25 °C
1
0 - 50 min
15
0 - 99 min
30
0 - 99 min
cL
cL - Ht
6
0 - 99 hours
30
0 - 99 min
it
rt – it – St – dF
备
Factory Setting
注
15℃
5°C
1
0
0
Ht
0
0
it