Huawei R100020G1 User Manual page 42

Charging module
Table of Contents

Advertisement

R100020G1 Charging Module
User Manual
Indicator
Fault
indicator
(red)
Note: If the alarm persists, contact the technical support.
Issue 05 (2021-11-16)
Status
Description
Communication failure
between the charging
module and external
devices
Output short circuit
alarm
Steady
Lockout due to output
on
overvoltage
Lockout due to output
short circuit
Communication failure
between the primary
side and the secondary
side
Abnormal discharge
circuit of the output
capacitance
Unrecoverable no-
output breakdown
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Maintenance
Troubleshooting
1. Check whether the CAN
communications cable and
build-out resistor are
correctly connected. If not,
rectify the fault.
2. Exchange the slot of the
faulty module with that of a
normal module. If the fault
occurs only in the original
slot, the slot is abnormal and
needs to be handled.
3. Exchange the slot of the
faulty module with that of a
normal module. If the fault
occurs again after the slot
exchange, replace the faulty
module or contact the
technical support.
1. Check whether the output
port of the charging module
is short-circuited.
2. Replace the faulty module.
1. Check whether the air
channel of the charging
module is seriously blocked. If
yes, rectify the fault.
2. Check whether the output of
the charging module is short-
circuited. If yes, rectify the
fault.
3. Exchange the slot of the
faulty module with that of a
normal module. If the fault
occurs only in the original
slot, the slot is abnormal and
needs to be handled.
4. Exchange the slot of the
faulty module with that of a
normal module. If the fault
occurs again after the slot
exchange, replace the faulty
module or contact the
technical support.