R100020G1 Charging Module
User Manual
5
Powering On the Charging Module and
●
●
●
Issue 05 (2021-11-16)
After the installation is complete, power on the charging module. Use a
multimeter to check whether the voltage at the cabinet copper bar connected
to the output connector of the charging module is within the normal range
(150–500 V DC in low-voltage mode and 150–1000 V DC in high-voltage
mode).
Check that the power indicator on the charging module is steady on and the
voltage displayed on the nixie tubes is the same as that measured by the
multimeter.
Set the hardware address of the charging module if grouping is required.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Powering On the Charging Module and Setting
Setting Parameters