10
Commissioning
10.1
Power-On
Download the Service Expert app from HUAWEI AppGallery. The app can only run on
Android currently. You must apply for the permission to use the app after
downloading it.
Ensure that no combustion-supporting materials (air or additives) enter the air
conditioning system during commissioning. Huawei shall not be liable for any risks and
losses thus incurred.
Users are classified into admin and operator. The preset password is 000001 for both
types of users.
After powering on, the smart cooling product is in shutdown mode.
After powering on, the compressor starts preheating, and the system generates an
alarm indicating that the compressor is preheating (for 12 hours). Do not start the
smart cooling product before the preheating ends. Choose Running > Device Details
> Compressor to query the remaining preheating time.
1. Turn on the smart cooling product switch in the upstream power distribution frame (PDF).
2. Turn on the main switches.
3. After the device is powered on for the first time, the LCD displays the Quick Settings screen.
Set parameters as instructed, such as language, date format, date, time, and time zone. If the
device is not powered on for the first time, the home screen is displayed.