7 Setting and procedure for operation
7.5.2 How to connect wires
(1) Follow the wiring diagram for external connection to QE81WH.
(2) Use appropriate electric wires as described below.
At the connection between the secondary terminal of current (EMU-CT***,
EMU-CT***-A) sensor and
Applicable wire
(Usable electric wire)
(3) Stripping length of the used wire in use has to be 10 to 11 mm. Check the stripping
length using the strip gauge of QE81WH main module.
(4) When stranded wire is used, a bar terminal must be used.
Recommended bar terminal
(5) When attaching and detaching cables to/from the terminal, use the push button. Check
that the wire is securely inserted.
(6) Insert a wire to the terminal all the way until it touches the end.
, use twisted pair cable.
current input terminals
Single wire: AWG24 to AWG17 (φ0.5 mm to 1.2 mm)
Stranded wire: AWG20 to AWG16 (0.5 mm
TGV TC-1.25-11T (Made by Nichifu) or equivalent
7 - 7
2
to 1.3 mm
Stripping length of the wire
10 mm to 11 mm