6 Buffer memory
6.2.4 Current demand time (Un \ G3)
Set a time duration for which the average fluctuation of current demand is measured from the measured
current value.
If current demand time is set short, the response to change of current will be quick; however, the
fluctuation range may be too large. Adjust the duration according to the load and purposes.
(1) Setting procedure
(a) Set current demand time in the buffer memory.
- Configurable range: 0 to 1800 (seconds)
- Set the value in seconds.
(b) Turn Operating condition setting request (Yn9) from OFF to ON to enable the setting. (Refer to
5.2.2 (5).)
(2) Default value
It is set to 120 seconds.
6.2.5 Electric power demand time (Un \ G4)
Set a time duration for which the average fluctuation of electric power demand is measured from the
measured power value.
If electric power demand time is set short, the response to change of power will be quick; however, the
fluctuation range may be too large. Adjust the duration according to the load and purposes.
(1) Setting procedure
(a) Set electric power demand time in the buffer memory.
- Configurable range: 0 to 1800 (seconds)
- Set the value in seconds.
(b) Turn Operating condition setting request (Yn9) from OFF to ON to enable the setting. (Refer to
5.2.2 (5).)
(2) Default value
It is set to 120 seconds.
6 – 9