Appendix 2: Optional devices

(1)Specifications
Split type current sensor
Item
Model
Rated primary current
Rated secondary current
Rated burden
Maximum voltage
(voltage to ground/line voltage)
Ratio error
Phase displacement
Measurement(installation)category
Pollution degree
Working temperature range
Working humidity range
CE marking conformity standard
CE marking conformity standard
Maximum voltage
(voltage to ground/line voltage)
Weight (per one)
*Use an electric wire of the size of penetrating this current sensor for a primary side cable, do not use a non-insulation
electric wire or a metal for a primary cable.
*EMU-CT400 and EMU-CT600 are stopped.
Item
Model
Rated primary current
Rated secondary current
Rated burden
Maximum voltage
(voltage to ground/line voltage)
Ratio error
Phase displacement
Measurement(installation)category
Pollution degree
Working temperature range
Working humidity range
CE marking conformity standard
CE marking conformity standard
Maximum voltage
(voltage to ground/line voltage)
Weight (per one)
*Use an electric wire of the size of penetrating this current sensor for a primary side cable, do not use a non-insulation
electric wire or a metal for a primary cable.
EMU-CT50
EMU-CT100
50 A AC
100 A AC
16.66 mA
33.33 mA
±1 %(5 % to 100 % of rating, RL≦10 Ω)
±30 min.(5 % to 100 % of rating, RL≦10 Ω)
−5 °C to +55 °C (daily mean temperature: +35 °C or less)
5 % to 95 %RH (no condensation)
0.1 kg
EMU-CT50-A
EMU-CT100-A EMU-CT250-A EMU-CT400-A EMU-CT600-A
50 A AC
100 A AC
16.66 mA
33.33 mA
±1 %(5 % to 100 % of rating, RL≦10 Ω)
±45 min. or less(10 % to 100 %
of rating, RL=10 Ω)
±60 min. or less(5 % of rating,
RL=10 Ω)
-
-
−5 °C to +55 °C (daily mean temperature: +35 °C or less)
30 % to 85 %RH (no condensation)
-
-
0.1 kg
0.1 kg
Appendix - 2
Specifications
EMU-CT250
EMU-CT400
250 A AC
400 A AC
66.66 mA
66.66 mA
0.1 VA
460 V AC
|||
2
EN61010-2-032
460 V AC
Specifications
250 A AC
400 A AC
66.66 mA
66.66 mA
0.1 VA
460 V AC
±40 min. or less
(5 % to 100 %
±40 min.(5 % to 100 %
of rating,
of rating, RL≦10 Ω)
RL=10 Ω)
0.2 kg
0.3 kg
QE81WH
EMU-CT600
600 A AC
66.66 mA
0.7 kg
600 A AC
66.66 mA
|||
2
EN61010-2-032
460 V AC
0.4 kg