ABB Emax 2 Installation And Maintenance Manual page 48

Direct/cic replacement of legacy ge ak 600a - 4000a circuit breakers used in akd-5 & substructures
Table of Contents

Advertisement

Figure 92
3. To install OEM Door Adaptor Follow the instructions below:
Figure 93
48| © 2020 Emax 2 Retrofill Circuit Breakers 600A-4000A
Door Interior View
De-energize/switch off the LVS section that is to be retrofitted.
Open the compartment door that is to be retrofitted.
Rack out & Remove the existing legacy AK/AKR breaker from the LVS.
Unpack the new door Adaptor kit assembly
Modify the door cut out as per the new door cutout template.
Check the through-door racking with the new door assembly.
Insert the new retrofitted Emax 2 Retrofill circuit breaker into the compartment and
slide the breaker into the disconnected condition.
Close the door and secure it to the compartment.
Rack-in the new retrofitted Emax 2 Retrofill Breaker.
For detail instructions refer document 2TSE431967R1000, 2TSE431968R1000 &
2TSE431996R1000
OEM Adaptor (Show as Example)
Door Exterior View
2TSA451011P0000 Rev-B