Bosch CL400 Manual page 38

Hide thumbs Also See for CL400:
Table of Contents

Advertisement

4- -2
R5INIT
4.2.1
Input Parameters
Parameter
Attribute
P0
W
P1
W
P2
W
P3
W
P4
W
The module number corresponds to the line number of the entry in the sys-
tem table. (This is not the block address!)
The assignment of the computer interface number (RSS no.) to the module
number can be chosen freely.
If the module number is passed to the parameter P2 e.g., the RSS no. is = 2.
If the module numbers of the computer interfaces are changed in the SK
table, the parameters of the R5INIT must be adjusted accordingly. For those
modules that are not available in the system, the value 16#FFFF must be
passed as a parameter.
Because this module may be called up only once in any ZS Central Unit, one
call initializes all communication modules (R500, R500P, COM-P, COM-E,
R500MAP and R500M-EN) that are supposed to execute the data commu-
nication jobs of the corresponding ZS.
Description
Module number of computer interface 0
Module number of computer interface 1
Module number of computer interface 2
Module number of computer interface 3
Module number of computer interface 4
1070 072 196-101 (00.06) GB