Mitsubishi Electric 800 Series Instruction Manual page 37

Compact, high functionality inverters
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 Safety communication model
Source logic
Main circuit terminal
Control circuit terminal
MCCB
Three-phase
AC power
supply
24 VDC power supply
Safety input terminal common
Safety input (channel 1)
Safety input (channel 2)
24 VDC power supply common
Frequency setting signals (Analog)
Connector for
plug-in option connection
*1
Remove the jumper between P1 and P/+ to connect the DC reactor.
*2
Terminal input specifications can be changed by analog input specification switchover (Pr.73, Pr.267). To input voltage, set the voltage/current
input selection switch to "V". To input current, set the switch to "I". The initial setting varies depending on the specification. (Refer to the FR-E800
Instruction Manual (Function).)
*3
It is recommended to use 2 W 1 kΩ when the frequency setting signal is changed frequently.
*4
The function of these terminals can be changed using the Pr.192 ABC??????.
36
2. Installation and Wiring
2.4 Terminal connection diagrams
Earth
(Ground)
MC
R/L1
S/L2
T/L3
Earth
(Ground)
PC
SX1
SX2
SD
10(+5V)
3
Frequency
setting
2 0 to 5VDC
2
potentiometer
1/2W1kΩ

5(Analog common)
1
4 4 to 20mADC
Terminal 4 input
(+)
(Current input)
(-)
Voltage/current
input switch
Brake unit
DC reactor
(Option)

R
PR N/-
Jumper
P1
P/+
Main circuit
Control circuit
24V
Ethernet
connector
Ethernet
connector
0 to 5VDC

0 to 20mADC
USB mini B
connector
0 to 5VDC

0 to 10VDC
2
V
I
4

Option connector
V
W
C
B
Relay output
(Fault output)
A
Safety communication function selection
SY1
Safety output (channel 1)
SC1
Safety output common (channel 1)
SY2
Safety output (channel 2)
SC2
Safety output common (channel 2)
Motor
M
Earth (Ground)
Relay output 

Advertisement

Table of Contents
loading