4. Rotary switch function

Item
SW
SW1
Yellow
Interface address
SW2
Reserve
Yellow
SW3
Red
Reserve
RotarySW
SW4
Reserve
Red
SW5
Yellow
Modbus address (ones)
SW6
Yellow
Modbus address (tens)
・Set master and slave by SW1.
・For a single refrigerant system, always set the address of AHU interface to 0.
・For cascade control, set the master address to 0 and the slave address to a value other than 0 (1 to F).
・Rotary SW5 and SW6 are address settings for Modbus communication.
SW5 is Modbus address ones place and SW6 is Modbus address tens place.
In Modbus communication, AHU interface is a slave.
Set the Modbus address in 01 – 99 (Initial address setting: 01).
The Modbus address cannot be set to 0.
Contents
Remarks
0-F
Always 0
Always 0
Always 0
0-9
0-9
<Modbus address example>
Modbus address: 38
SW6: 3 SW5: 8
RotarySW
MODEL NAME
Air Handling Unit Interface
MODEL TYPE
AHU-KIT-SP
ISSUE
CLASSIFICATION
SPECIFICATION
MORIKAWA
DWG NO.
REV.MARK PAGE
PSZ000Z308
21.09.17
8/38