●Heat exchanger, minimum airflow and recommended circuits
・Be sure to select and set the capacity of the heat exchanger connected to each outdoor unit and the minimum air volume according to the following table.
・The table below is for both R 32 and R 410 A refrigerants.
・The range of use for air conditions conforms to the specifications of the outdoor unit.
Refer to the technical manual for the outdoor unit.
Allowable heat exchanger
volume
Outdoor unit
L
model capacity
Min
Max
SRC40
0.3
0.8
SRC50
0.3
0.9
SRC60
0.5
1.1
FDC71
0.7
1.6
FDC100
0.7
2.1
FDC125
1.0
2.2
FDC140
1.0
2.8
FDC200
1.2
4.2
FDC250
2.0
4.4
FDC280
2.0
4.4
・Recommended circuit number for D9.52 tube
Outdoor unit model capacity
40 50 60 71 100 125 140 200 250 280
2 〜 4
Recommended circuit
Minimum air volume
3
3
m
/h
m
/min
420
7
420
7
480
8
600
10
840
14
960
16
1080
18
1680
28
1920
32
2160
36
4 〜 6
6 〜 10
MODEL NAME
Air Handling Unit Interface
MODEL TYPE
AHU-KIT-SP
ISSUE
CLASSIFICATION
SPECIFICATION
MORIKAWA
DWG NO.
REV.MARK PAGE
PSZ000Z308
21.09.17
5/38