Output circuit

●Digital output circuit
・The digital output terminal output ON/OFF status.
・The functions of the digital output are as follows.
Terminal
Function
X4a
Outdoor unit/interface error
X4b
Compressor ON
X4c
Defrost ON
X4d
Function selectable*
●LED output circuit
・The LED output shows the normal/abnormal status of the system.
・LED 1 (green): blinks at 0.5 sec intervals during normal operation.
・LED 2 (red): flashes when abnormal (lights out when normal).
The number of flashes changes depending on the error status. For details, refer to (13) error display.

Input/output circuit

・Input/output functions are as follows.
Item
Connector Housing
X1
2P
Remote control
X5
3P
Modbus
Input/output
2P
Cascade control
X7
2P
Cascade control (reserve)
X0
5P
Power (X0-2 is an empty port)
・X5 : Modbus communication circuit terminal.
X5-1
A polor
X5-2
B polor
X5-3
GND
JX1
1–2: not available
(termination)
2–3: available 100Ω
・X7 : Cascade connection terminal.
However, X7-3 and X7-4 are reserve circuits.
ON
OFF
Error
Normal
Compressor ON
Compressor OFF
Defrost ON
Defrost OFF
Run
Stop
Function
(*) Setting of Xd4 can be changed by SW8 -1.
Digital Output:X4d
DipSW8-1
Function
ON
Operation mode output
Heating
Run/stop
OFF
(Fan ON/OFF)
(Fan ON)
Digital output
Voltage free a contact output
X4d
X4c
ON
OFF
Cooling
Run
Stop
(Fan OFF)
MODEL NAME
Air Handling Unit Interface
MODEL TYPE
AHU-KIT-SP
ISSUE
CLASSIFICATION
SPECIFICATION
MORIKAWA
DWG NO.
PSZ000Z308
21.09.17
X4b
X4a
REV.MARK PAGE
16/38