Low Voltage Directive
We have self-confirmed our inverters as products compliant to the Low Voltage Directive (Conforming standard EN 61800-5-
1) and affix the CE marking on the inverters.
 Outline of instructions
• Do not use an earth leakage current breaker as an electric shock protector without connecting the equipment to the
earth. Connect the equipment to the earth securely.
• Wire the earth terminal independently. (Do not connect two or more cables to one terminal.)
• Use the cable sizes on
• Ambient temperature: 40°C (104°F) maximum
If conditions are different from above, select appropriate wire according to EN60204 Appendix C TABLE 5.
• Use a tinned (plating should not include zinc) crimping terminal to connect the earth (ground) cable. When tightening
the screw, be careful not to damage the threads.
For use as a product compliant with the Low Voltage Directive, use PVC cable whose size is indicated on
• Use the moulded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard.
• DC current may flow from the inverter to a protective earth (ground) conductor. When using a residual current device
(RDC) or residual current monitor (RDM), connect a type B RCD or RCM to the power supply side.
• Use the inverter under the conditions of overvoltage category II (usable regardless of the earth (ground) condition of the
power supply), overvoltage category III (usable with the earthed-neutral system power supply, 400 V class only) and
pollution degree 2 or lower specified in IEC60664.
• On the input and output of the inverter, use cables of the type and size set forth in EN60204 Appendix C.
• The operating capacity of the relay outputs (terminal symbols A1, B1, C1, A2, B2, C2) should be 30VDC, 0.3A. (Relay
output has basic isolation from the inverter internal circuit.)
• Control circuit terminals on
• Environment (For the detail, refer to
Ambient temperature
Ambient humidity
Maximum altitude

For the installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude.
• Install the inverter at a place where ultraviolet radiation is not applied directly.
 Branch circuit protection
Class T, Class J, Class CC fuse, or UL 489 Molded Case Circuit Breaker (MCCB) must be provided.
FR-F846-[]
Rated fuse voltage (V)
Fuse allowable rating (A)
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
FR-F846-[]
Rated fuse voltage (V)
Fuse allowable rating (A)
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
 Short circuit ratings
• 400 V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 500 V Maximum.
page 29
under the following conditions.
page 21
are safely isolated from the main circuit.
page
18.)
During Operation
-10 to +40°C
95% RH or less
2500 m

00023
00038
00052
(0.75K)
(1.5K)
(2.2K)
500 V or more
6
10
10
15
15
15

00620
00770
00930
(30K)
(37K)
(45K)
500 V or more
125
150
175
150
175
225

In Storage
-20 to +65°C
95% RH or less
2500 m
00083
00126
00170
(3.7K)
(5.5K)
(7.5K)
15
25
35
20
30
40
01160
01800
02160
(55K)
(75K)
(90K)
200
250
300
250
450
450
page
During Transportation
-20 to +65°C
95% RH or less
10000 m
00250
00310
00380
(11K)
(15K)
(18.5K)
60
70
90
60
70
90
02600
03250
03610
(110K)
(132K)
(160K)
350
400
500
500
APPENDIX
29.
00470
(22K)
100
100
121