Mitsubishi Electric FR-F806-E Hardware Instruction Manual page 113

Inverter for fans and pumps, ip55/ul type 12
Table of Contents

Advertisement

Common specifications
Surrounding air
temperature
Surrounding air humidity
Storage temperature

Atmosphere
Altitude/vibration

This protective function is not available in the initial status.

Temperature applicable for a short time, e.g. in transit.
2

2.9 m/s
or less for the FR-F846-01800(75K) or higher.
112
SPECIFICATIONS
-10°C to +40°C (non-freezing)
With circuit board coating (conforming to IEC60721-3-3 3C2/3S2): 95% RH or less (non-condensing)
Without circuit board coating: 90% RH or less (non-condensing)
-20°C to +65°C
Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt, etc.)
Maximum 2500 m (for the installation at an altitude above 1,000 m, derate the rated current 3% per 500 m.), 5.9 m/s
less at 10 to 55 Hz (directions of X, Y, Z axes)
2
or

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents