Mitsubishi Electric LGH-50RVS-E Installation Instructions Manual page 22

Lossnay heat recovery ventilator
Hide thumbs Also See for LGH-50RVS-E:
Table of Contents

Advertisement

Night-purge setting 1)
No.30
Air volume
Set fan speed during Night-purge. To use Night-purge function, it is
necessary to set
,
No. 30
No. 31
This function is N/A from Lossnay unit DIP-SW.
When using PZ-62DR-E and AE-200E together, set all conditions
from AE-200E.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
N/A
30
-
-
-
-
-
-
Night-purge setting 2)
No.31
Outdoor and indoor temperature gap
Set one of conditions for Night-purge start, temperature gap between
indoor and outdoor.
When the actual gap between indoor and outdoor becomes bigger
than the setting, Night-purge starts.
This function is N/A from Lossnay unit DIP-SW.
When using PZ-62DR-E and AE-200E together, set all conditions
from AE-200E.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
N/A
31
-
-
-
-
-
-
-
-
Night-purge setting 3)
No.32
The lowest outdoor temperature
Set one of conditions for Night-purge start, maximum outdoor
temperature within 72 hours.
When this setting temperature is low, it is likely to start Night-purge.
This function is N/A from Lossnay unit DIP-SW.
When using PZ-62DR-E and AE-200E together, set all conditions
from AE-200E.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
N/A
32
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
,
correctly.
No. 32
Setting
Air volume
check
N/A (Night-purge
0
(Factory setting)
function is not available)
1
Fan speed 1
2
Fan speed 2
3
Fan speed 3
4
Fan speed 4
Setting
Outdoor and indoor
check
temperature gap
0
0 K (0˚C) or more
1
1 K (1˚C) or more
2
2 K (2˚C) or more
3
3 K (3˚C) or more
4
4 K (4˚C) or more
5
5 K (5˚C) or more
(Factory setting)
6
6 K (6˚C) or more
7
7 K (7˚C) or more
Setting
The lowest outdoor
check
temperature
0
15˚C or more
1
16˚C or more
2
17˚C or more
(Factory setting)
3
18˚C or more
4
19˚C or more
5
20˚C or more
6
21˚C or more
7
22˚C or more
8
23˚C or more
9
24˚C or more
10
25˚C or more
11
26˚C or more
12
27˚C or more
13
28˚C or more
14
29˚C or more
15
30˚C or more
Night purge setting 4)
No.33
Outdoor temperature detection period
Night-purge is decided to start or not by the OA temperature within X
hour.
X hour can be selected from 24, 48 or 72 hr.
It is possible to operate Night-purge on Sunday midnight or Monday
early morning by select longer setting even Lossnay stops.
When using PZ-62DR-E and AE-200E together, set all conditions
from AE-200E.
DIP-SW
Setting
check
SW No.
Setting
-
-
N/A
-
-
No.34
Input priority setting
Set to follow input to the main unit from air conditioner, fan speed
controller, etc.
When multiple Lossnay units fan speed is externally controlled via
CN17 or CN26, select individual control or bunch control.
When bunch control is selected, connect PZ-62DR-E and input
external signal to the main unit.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
SW No.
Setting
-
-
N/A
-
-
No.36
Outdoor temperature display setting
Set to display outdoor temperature detected by Lossnay unit
thermistor.
This function is N/A from Lossnay unit DIP-SW.
This function is available only when "Sensor value" is set to "Yes"
(Display) by the remote controller PZ-62DR-E.
DIP-SW
Setting
check
SW No.
Setting
-
-
N/A
-
-
No.37
Indoor temperature display setting
Set to display indoor temperature detected by Lossnay unit thermistor.
This function is N/A from Lossnay unit DIP-SW.
This function is available only when "Sensor value" is set to "Yes"
(Display) by the remote controller PZ-62DR-E.
DIP-SW
Setting
check
SW No.
Setting
-
-
N/A
-
-
Eng-22
PZ-62DR-E
Setting
OA temperature
check
detection period
Function No. Setting Data
0
24 hrs
1
48 hrs
33
2
72 hrs
(Factory setting)
PZ-62DR-E
Setting
Input priority setting
check
Function No. Setting Data
0
Bunch control priority
(Factory setting)
34
1
Individual control priority
PZ-62DR-E
Setting
Outdoor temperature
check
display
Function No. Setting Data
0
N/A
36
1
Available on the screen
(Factory setting)
of PZ-62DR-E
PZ-62DR-E
Setting
Indoor temperature
check
display
Function No. Setting Data
0
N/A
37
Available on the screen
1
(Factory setting)
of PZ-62DR-E

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: