When interlocked with indoor unit of air conditioner or
other external device including other manufactures
CAUTION
• The connection may vary according to the output signal type
of the external unit.
• Do not press the terminal with a force of more than 19.6 N
when connecting the cable to TM2.
Lossnay
TM2
Power supply
When using Mitsubishi Mr. Slim air conditioner with MA
Remote controller
Confirm that the pulse input switch (SW2-2) is set to "OFF".
(Factory setting is "OFF".) (Refer to function settings
Connect the Slim-Lossnay connection cable connector side to
CN2L on the circuit board for the Mr. Slim indoor unit, then connect
the lead wire side to the 1 and 2 of the input terminal block (TM2)
for the Lossnay external controller input. (No polarity)
• Always separate the power supply cable and the Slim-Lossnay
connection cable by 5 cm or more to prevent the unit from
malfunctioning.
• The Slim-Lossnay connection cable is 100 mm long. When
wiring, extend it as far as necessary.
1 2
Y Z
Lossnay external
control input
(TM2)
Maximum 50 m
Note
• Use MA remote controller of Mr. Slim for switching Lossnay
ON/OFF or the fan speed.
• The ventilation mode is fixed to "automatic ventilation" from
MA remote controller.
• Ensure that all connections are secure and that the appropriate
insulation is provided.
Use extension cable sheathed PVC cable or cable 0.5 mm
1.5 mm
.
2
• Only one Lossnay and one Mr. Slim unit can be interlocked.
Multiple units interlock is not possible.
• Lossnay can not be connected M-NET in this case.
[SW2-2] setting vary depending on the types of output signal of
external device.
When the external device has a charged operating signal
of 12 VDC or 24 VDC
• If the input is pulse signal, move the pulse input switch [SW2-2]
to the ON position. (Refer to function settings
• When level signal is selected, the signal width has to be more
than 10 seconds for ON and OFF .
• When pulse signal is selected, a pulse width has to be at least
200 m sec. to turn Lossnay ON, and 10 sec. interval is necessary
to next output.
• The wiring should be as shown by the following picture.
Lossnay external
1 2
Y Z
control input
(TM2)
Overall connection extension length
(Follow the operation manual for the external equipment.)
External
device
Power supply
Operating switch
for external device
No. 28
Slim-Lossnay connection cable
(Accessory parts)
CN2L
Mr. Slim (Indoor unit)
Printed circuit board
)
No. 28
0.5 mm
to 1.5 mm
sheathed PVC cable
2
2
External device
12 or 24 VDC
When the external device has an Volt-free contact signal
• If the input is pulse signal, move the pulse input switch [SW2-2]
to the ON position. (Refer to function settings
• When level signal is selected, the signal width has to be more
than 10 seconds for ON and OFF .
• When pulse signal is selected, a pulse width has to be at least
200 m sec. to turn Lossnay ON, and 10 sec. interval is necessary
to next output.
• The wiring should be as shown by the following picture.
1 2
Y Z
CAUTION
• If an optocoupler or any other type of polar coupler is used at
)
the Volt-free contact, connect the positive side to
negative side to
3
When operating multiple Lossnay units
In the case that all Lossnay units are the same LGH-RVS-E series,
up to 15 multiple units can be operated at the same time.
1) Connect the Lossnay unit from Unit 1 to Unit 2, and from Unit 2 to
Unit 3 and so on up to a maximum of 15 units using a transmission
cable.
Wire type: two-core sheathed cable
Wire diameter: 0.3 mm
2) When it is interlocked with an external device, set the Lossnay unit
which has external signal input to "Main".
Lossnay
Power supply
Lossnay
to
2
Power supply
Lossnay
Power supply
MAX 15 units
CAUTION
• Do not tighten screws of terminal block with a torque larger
than 0.5 N . m. It could damage the circuit board.
Eng-12
Lossnay external
0.5 mm
to 1.5 mm
2
control input
(TM2)
External device
Volt-free contact
Maximum 500 m
.
Z
2
Remote controller
(PZ-62DR-E)
External
device
Power supply
Operating switch for
external device
First
TM4
1
2
Lossnay
Second
TM4
Lossnay
1
2
Transmission cable
)
No. 28
sheathed PVC cable
2
and the
Y
Connect to
remote controller
(PZ-62DR-E)
Connect to
third Lossnay

Hide quick links: