Mitsubishi Electric LGH-50RVS-E Installation Instructions Manual page 21

Lossnay heat recovery ventilator
Hide thumbs Also See for LGH-50RVS-E:
Table of Contents

Advertisement

Delay start setting for air conditioner
No.9
starting
Delays Lossnay operation for 30 minutes when City Multi or Mr. Slim
starts operating or when a external device starts operating.
This function is available only when Lossnay is interlocked with air
conditioners.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
OFF
SW2-3
9
(Factory setting)
-
-
ON
No.12-16
Monitor output setting
Set operation monitor output from TM3 90 synchronized with fan
operation, ventilation mode or occurrence of malfunction.
Monitor output setting for PZ-4GS-E COM-OUT1 to 4 can be set from
the remote controller as well.
DIP-SW
Setting
Setting
check
SW No.
Function
Function
Function
No.12
No.13-16
-
-
-
5-1 OFF
5-2 OFF
-
(Factory setting)
5-1 ON
-
5-2 OFF
SW5-1
SW5-2
5-1 OFF
-
5-2 ON
5-1 ON
-
5-2 ON
Setting
Lossnay delay start
check
0
DIP-SW priority
(Factory setting)
1
N/A
2
15 min
3
30 min
PZ-62DR-E
Setting
Monitor output
Setting
check
setting
Function
No.12
No.13-16
0
-
DIP-SW priority
Operation monitor output
The output turns
1
0
ON
*1
while Lossnay is
operating.
Malfunction monitor
output
The output turns ON
2
1
when a malfunction
occurs on the Lossnay
unit.
By-pass ventilation
operation monitor output
3
2
Corresponds to operation
mode output of the By-
pass damper.
SA fan monitor output
* When supply fan stops
4
3
due to cold outdoor temp.
or defrosting, output stops.
5
4
EA fan monitor output
Pre-heater output
Output starts 10 seconds
after supply fan starts
operation.
Fan continues to operate
for 3 min. after stopping
the output.
Lossnay starts output
when outdoor temp. is
0˚C or less, and stops
output when detecting
temp. becomes 15˚C.
6
5
Lossnay stops the output
every 1 hour. Error code
is shown on the remote
controller and the output
stops in the case of
following.
1) Outdoor temperature
higher than 15˚C within
15 minutes after the
output starts.
2) Outdoor temperature
-10˚C or lower, 5 minutes
after the output starts.
SA fan monitor output
with delay operation (for
After heater)
Output starts 10 seconds
7
6
after supply fan starts
operation.
Fan continues to operate
for 3 min. after stopping
the output.
- To use as the after-heater output, observe the cautions listed in 4
in the page 13.
- For heater selection, observe the cautions listed in 4 in the page
13.
Exhaust fan setting during air conditioner
No.17
defrosting
This function can be used under the condition Lossnay supply duct is
connected to Mr. Slim or City Multi indoor unit.
Sets the operation of the exhaust fan during defrosting of the air
conditioner (when supply fan stop).
To enable this function, it is necessary to set the indoor unit also.
Please refer to its manual.
DIP-SW
Setting
check
SW No.
Setting
OFF
-
(Factory setting)
SW5-3
ON
-
No.19
Interlock mode setting
These settings indicate how Lossnay should operate when City Multi
or external devices are started or stopped.
DIP-SW
Setting
check
SW No.
Setting
-
-
*1
-
-
N/A
-
-
-
-
No.28
Pulse input setting
Set external input signal type from external device for TM2.
DIP-SW
Setting
check
SW No.
Setting
-
-
OFF
SW2-2
(Factory setting)
ON
When pulse signal is selected, No. 9 and No. 19 are not available.
Keep factory settings for No. 9 and No. 19.
Either interlocking with City multi or Mr. Slim is not possible.
Eng-21
PZ-62DR-E
Setting
Exhaust fan operation during
check
air conditioner defrosting
Function No. Setting Data
0
No change
17
1
Stop
2
DIP-SW priority
(Factory setting)
PZ-62DR-E
Setting
Interlock setting
check
Function No. Setting Data
The Lossnay will start and stop
according to the operation of the
external devices. Subsequent
0
(Factory setting)
operation will be possible using
the remote controller for the
Lossnay or MELANS.
The Lossnay will start whenever
external devices are operated.
1
Stopping Lossnay operation
will be possible using its remote
controller or MELANS.
19
The Lossnay will stop whenever
external devices are stopped.
2
Starting Lossnay operation will
be possible using its remote
controller or MELANS.
The Lossnay will start and stop
according to the operation of
the external devices. Control
3
via the Lossnay remote
controller or MELANS will only
be possible when external
devices are stopped.
PZ-62DR-E
Setting
Pulse input setting
check
Function No. Setting Data
0
DIP-SW priority
(Factory setting)
28
1
NOT pulse input
2
Pulse input