Failures At Brake, Fuse Or Wiring - ABB LME620AI Service Instruction

Electrical linear actuators for continuous modulating control
Hide thumbs Also See for LME620AI:
Table of Contents

Advertisement

10.2 Failures at brake, fuse or wiring

E2.2: Motor / brake wiring acc. to wiring diagram? (see chpt. 6.3
R 2.2:
Correct
wiring
24
Electrical Linear Actuators for Continuous Modulating Control LME620AI / LME620AN (Contrac)
E 2.1: actuator can be moved
E1.1: Yes
over entire range via drive but-
tons on LCP
No
No
E 2.3: Disconnect actuator and valve. Actuator can be moved?
R 2.3:
R 2.4:
Motor de-
Adjust
fective
brake gap
Yes
R 2.1 See 10.3
Yes
Yes
No
E3.4:Motor winding resistance
acc. to table 3
No
Yes
E 3.5: Check brake. „Click
sound" audible?
No
Yes
E 3.7: Remove motor (Oil!) Gearing
smoothly rotable over entire range?
No
R 2.6:
Act. runs
mech.
hard
Trouble Shooting
Yes
R 2.7:
R 2.8:
Motor
/
Valve runs
brake
hard
defective
43/68-13 EN